Programming
Overview
Before the FloTech FT203P Monitor can be put into service, it
must be programmed. This procedure informs the monitor
which inputs have sensors attached. These inputs are then
labeled as ACTIVE sensors. The remaining inputs that do NOT
have sensors attached are labeled as INACTIVE inputs. This
insures that a PERMIT signal will be issued only if ALL of the
following conditions are met:
All active overfill sensors are dry.
All inactive overfill sensors are not connected.
All active retain sensors are dry or the Timer/Reset
button has been pressed.
All inactive retain sensors are disconnected.
The AUX input has a jumper or made through an
external switch contact.
If ANY of the above conditions are not met, the PERMIT signal
will not be generated.
Procedure
1)
Turn the power off to the monitor.
2)
Remove the reset switch wires from TB5.
3)
Connect the programming module per Fig. 8.
Fig. 8
Program Module Position