www.flowair.com |10
5. CONTROL SYSTEMS
DRV CONTROL
:
Connecting curtains
– controlling up to 5 units with one controller;
Connecting to curtain room thermostat*, door contact*, valves with actuator*, speed controller*;
*optional equipment
5.1. CONTROL ELEMENTS
TS - 3-speed fan switch with
room thermostat
Temperature range::
+10 … +30
o
C
Operatiing temperature range:
0 … +40
o
C
IP/Insulation class:: IP30
Max current:
inductive 5A, resistive 6A
Power supply: 230V/50Hz
TA - 3-speed fan switch
Operating temperature
range:
0 … +40
o
C
IP/Insulation class: IP30
Max current:
inductive 4A, resistive 6A
DCm
– mechanical door contact
Operating temperature range:: -10 -
+80
o
C
IP/Insulation class: IP 65
Connectors: 1xNC i 1xNO
Max current:
resistive 10A
– inductive 3A
Max Power load: 300Vac or
250Vdc
DCe
– magnetic door
contact
Operating temperature
range::
-5 - +60
o
C
IP/Insulation class: IP 64
Connectors: NC
Max current::
inductive/resistive 0,5A
Max power Load: 175Vdc
Lenght of cabel: 2m
Max operating contactors
distance: 8mm
SRQ3d ½” – three-way 1/2 valve
with actuator
IP/Insulation class: IP20
Power supply:
200
– 240V 50/60Hz
Max water temperature: +93
o
C
Max water pressure
: 2,1MPa
Kvs: 3,4 m
3
/h
Opening time: 18 s
SRQ2d
½” – two-way 1/2
valve with actuator
IP/Insulation class: IP20
Power supply:
200
– 240V 50/60Hz
Max water temperature:
+93
o
C
Max water pressure
: 2,1MPa
Kvs: 3,0 m
3
/h