Typical Current Input Schematic
Voltage Input
Input Impedance:
100K
Ω
Range:
0-5V, 0-10V
Resolution:
±
0.024% FS
Typical Voltage Input Schematic
5.12 RTD Temperature Inputs
Compatible RTD type:
100
Ω
Platinum
(a = 0.00385: DIN 43-760 Calibration)
Suitable for use with:
2, 3 or 4 wire RTD's
Excitation Current:
2mA typical
Max Fault Current:
15mA
Max Voltage on sense inputs: 50 VDC
Rejection of 50 or 60Hz signal: 40dB (minimum)
(Automatically based on line frequency)
Raw Accuracy:
0.5C
°
Temperature Range:
-323.5 to +1378.7
°
F
( -197.5 to +748.1
°
C )
Lead Wire Compensation:
4 Wire
Four wire field wiring required for 2,3 and 4 wire RTD's
See schematic next page.
5-2