2
Table 4.31 – Continued
Attribute ID Access Rule Name
Data
Type
Description of
Attribute
Semantics of Value
21
Get/Set
(V-RW)
DO_ESD_
Poll_Cnxn
BOOL
Command emer-
gency shutdown
from
Poll Connection
Section 4.2.9
22
Get/Set
(V-RW)
DO_ESD_
Bit_Strobe_Cnxn
BOOL
Command emer-
gency shutdown
from
Bit-Strobe
Connection
Section 4.2.9
23
Get/Set
(NV-RW)
Enable_
Broadcast_
ESD_Ctrl
BOOL
Enable device to
be a part of the
broadcast
ESD control scheme
from Bit-Strobe
Connection
Section 4.2.9
0 = Disable (Default)
1 = Enable
4.4 Transducer Block Object
Table 4.32
Attribute ID Access Rule Name
Data Type
Description
Semantics of Value
1
RW
Setp_Cutoff_Dec
UINT
When the servo
setpoint goes below
the defined percent
of span, the position
goes to the limit
position CLOSE
Range 0 – 1000
Default = 0
2
RW
Setp_Cutoff_Inc
UINT
When the servo
setpoint goes above
the defined percent
of span, the position
goes to the limit
position OPEN
Range 0 – 1000
Default = 0
3
RO
Scaled_values_0
WORD
APT/ATT scaling
information
See Table 4.33
4
RO
Scaled_values_1
WORD
APT (Modbus
Register 3)
Engineering Use
5
RO
Scaled_values_2
WORD
ATT (Modbus
Register 4)
Engineering Use
6
RO
TP_Status_0
UINT
Reserved
Engineering Use
7
RO
TP_Status_1
UINT
Start_Position
Engineering Use
8
RO
TP_Status_2
UINT
Stop_Position
Engineering Use
9
RO
TP_Status_3
UINT
Num_Samples
Engineering Use
10
RO
TP_Status_4
UINT
Max_Torque_Mid
Engineering Use
11
RO
TP_Status_5
UINT
Max_Torque
Postion
Engineering Use
12
RO
TP_Status_6
UINT
Avg_Torque
Engineering Use
13
RO
TP_Status_7
UINT
Stop_Torque
Engineering Use
14
RO
TP_Status_8
UINT
Max_Torque_BOT
Engineering Use
15
RO
TP_Status_9
UINT
Maz_Torque_EOR
Engineering Use
16
RO
TQ_Status_0
UINT
Reserved
Engineering Use
17
RO
TQ_Status_1
UINT
MB_TQ_Close_
Avg_Last
Engineering Use
18
RO
TQ_Status_2
UINT
MB_TQ_Open_Avg_
Last
Engineering Use
19
RO
TQ_Status_3
UINT
MB_TQ_Open_
Peak_Last
Engineering Use
Continued on next page