Table 4.32 – Continued
Attribute ID Access Rule Name
Data Type
Description
Semantics of Value
41
RW
Valve_Type
USINT
Type of valve
0 = linear moving
valve, sliding valve
(Default) 1 = rotary
moving valve, part-
turn 2 = rotary moving
valve, multi-turn
42
RO
Actuator_Type
USINT
Type of actuator
0 = electropneumatic
1 = electric (default)
2 = electrohydraulic 3
= others
43
RO
Diagnostic_ Values_0
UINT
Reserved
Engineering Use
44
RO
Diagnostic_ Values_1
UINT
Main Voltage
Engineering Use
45
RO
Diagnostic_ Values_2
UINT
Actuator Position
Engineering Use
46
Diagnostic_ Values_3
UINT
Analog input #1
Engineering Use
47
Diagnostic_ Values_4
UINT
Analog Input #2
Engineering Use
48
RW
Tag_Name
SHORT-
STRING
Tag name for
generic use
String length is limited
to 32 char. Default = 0
(empty)
49
Get/Set
(NV-RW)
Comm_Loss_
Action
USINT
Actuator action
upon detection of
communication loss
0 = No Action
(Default)
1 = Open
2 = Close
3 = Stop
4 = Preset Position
50
Get/Set
(NV-RW)
Comm_Loss_
Position
UINT
Position to take
upon a communica-
tion loss
Range = 0 – 1000
Default = 0
51
Get/Set
(NV-RW)
Comm_Loss_
Timeout
UINT
Time to wait
after detection of
communication loss
until actuator action
is taken
Range = 0 – 4095
Default = 255
52
Get/Set
(NV-RW)
Deadband
UINT
Deadband
percentage to use
when positioning
Range = 0 – 1000
Default = 2
53
Get/Set
(NV-RW)
Proportional_
Band
UINT
Proportional band
percentage to use
when positioning
Range = 0 – 1000
Default = 8
54
Get/Set
(NV-RW)
TQ_Switch_
Adjust
USINT
Percentage of full
torque to limit
operation to
Range = 0 – 100 %
Default = 0 (Disabled)
55
RW
Actuator_Control_
Mode
USINT
Configure actuator
for open/close
or positioning
operation
1 = Analog
(Positioning Mode)
2 = Digital (Open/
Close Mode)
Default = 2
NOTE: Attributes 49-55 are reserved for Revision 1 to DeviceNet.
Table 4.33 – Transducer Attribute – Scaled values attribute 3
Bit 7 - 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Unused
DDC Offset
0 = 0 mA 1
= 4 mA
ATT Polarity
0 = high
value 4 mA
1 = high
value 20 mA
Analog
Torque
Transmitter
(ATT) 0
= ATT
Disabled 1 =
ATT Enabled
APT Polarity
0 = high
value 4 mA
1 = high
value 20 mA
Analog
Position
Transmitter
(APT) 0
= APT
Disabled 1 =
APT Enabled