11.2 PMV D20 symptoms and solutions
Failure
Probable Cause
Corrective action
No LED is flashing
Current source below 3,6 mA .
Verify current source
supplies at least 3,6 mA.
Incorrect wiring polarity.
Check wiring for correct
polarity.
Valve position reading
Stem position sensor mounting
Reposition sensor.
is not what is expected. is off 180 degrees.
Stroke not calibrated.
Calibrate stroke.
Tight shutoff MPC (Minimum
No action.
position cutoff) is active.
Custom characterization or soft
No action.
stops active.