Page 26
FW-F011-A-M_v0404_01_EN.docx
4.6.2
TERMINAL 4-5: POWER SUPPLY - TYPE PX (DEFAULT) AND PD (OPTION)
To power the F011-A an internal battery can be used (type PB) and / or an external DC power
supply of 8-30V DC (type PX) or 16-30V DC (type PD).
Connect the "
-
" to terminal 4 and the "
+
" to terminal 5.
When power is applied to these terminals, the optional internal battery will be disabled / enabled
automatically to extend the battery life time.
4.6.3
TERMINAL 9-10: POWER SUPPLY BACKLIGHT - TYPE ZB (OPTION)
To power the backlight, a voltage in the range 20-30V DC has to be connected.
Maximum current 30mA. Connect the "
-
" to terminal 9 and the "
+
" to terminal 10.
Fig. 16: Terminal connections - Backlight (ZB).
4.7
TERMINAL CONNECTORS SAFE AREA APPLICATIONS
– TYPE PF / PM
Take careful notice of all safety and precautionary measures indicated in paragraph
4.5: Electrical Installation and review paragraph 4.5.3 and 4.5.4 before applying any
field or power supply wiring.
For Intrinsically Safe applications: read chapter 5.
Following terminal connectors are available on the F011-A when supplied with Type PF / PM:
Fig. 17: Overview of terminal connectors F011-A
– type PF / PM
4.7.1
TERMINAL GND-1-2: POWER SUPPLY
To power the F011-A with a power supply option of type PF or type PM, connect a suitable power
supply to the terminals as indicated in below table:
Power supply
option
Power supply
Terminal
GND
01
02
Type PF
24V AC
10%
AC
AC
Type PF
24V DC
10%
L-
L+
Type PM
115-230V AC
10%
AC
AC
The total consumption of the sensor and backlight type ZB may not
exceed 400mA@24V DC.
GND
1
POWER SUPPLY
TYPE:
PF / PM
N
L1
2
SENSOR SIGNAL
TYPE: A
ANALOG (0)4-20mA
+
6
5
7
I