background image

 

HF070AEN_v0403_03 Atex_IECEx_CSA_FM

 

Page  30

6. MAINTENANCE 

 

6.1. GENERAL 

DIRECTIONS 

 
 

 

Mounting, electrical installation, start-up and maintenance of the instrument may only 
be carried out by trained personnel authorized by the operator of the facility. Personnel 

must read and understand this Operating Manual before carrying out its instructions. 

 

The F070-A may only be operated by personnel who are authorized and trained by the 

operator of the facility. All instructions in this manual are to be observed. 

 

Ensure that the measuring system is correctly wired up according to the wiring 

diagrams. Protection against accidental contact is no longer assured when the housing 
cover is removed or the panel cabinet has been opened (danger from electrical shock). 

The housing may only be opened by trained personnel. 

 

Take careful notice of the " Safety rules, instructions and precautionary measures " in 

the front of this manual. 

 
 
 
The F070-A does not require special maintenance unless it is used in low-temperature applications 
or surroundings with high humidity (above 90% annual mean). It is the users responsibility to take all 
precautions to dehumidify the internal atmosphere of the F070-A in such a way that no condensation 
will occur, for example by placing dry silica-gel sachet in the casing just before closing it. 
Furthermore, it is required to replace or dry the silica gel periodically as advised by the silica gel 
supplier. 
 
 

Battery life-time:  

It is influenced by several issues : 
 

  Display update: fast display update uses significantly more power. 

  Low temperatures; the available power will be less due to battery chemistry. 

 

Note:

 It is strongly advised to use only necessary functions. 

  
 
 

Check periodically: 

  The condition of the casing, cable glands and front panel. 

  The input/output wiring for reliability and aging symptoms. 

  The process accuracy. As a result of wear and tear, re-calibration of the sensor might be 

necessary. Do not forget to re-enter any subsequent span alterations. 

  The indication for low-battery. 

  Clean the casing with soapy-water.  Do not use any aggressive solvents as these might damage 

the coating. 

 
 

6.2. REPAIR 

 

This product cannot be repaired by the user and must be replaced with an equivalent certified 
product. Repairs should only be carried out by the manufacturer or his authorized agent. 

Summary of Contents for F070-A

Page 1: ...F070 A LEVEL INDICATOR Signal input sensor 0 4 20mA Options Intrinsically Safe F Series Field mounted indicators for safe and hazardous areas More info www fluidwell com fseries...

Page 2: ...disposed of according to local regulations regarding waste electronic equipment If a battery is present in this product it should be disposed of separately The separate collection and recycling of you...

Page 3: ...cedures which if not performed correctly may lead to personal injury a safety hazard or damage of the F070 A or connected instruments A caution indicates actions or procedures which if not performed c...

Page 4: ...t 14 5 Sensor 15 6 Others 16 4 Installation 17 4 1 General directions 17 4 2 Installation surrounding conditions 17 4 3 Dimensions Enclosure 18 4 4 Installing the hardware 20 4 4 1 Introduction 20 4 4...

Page 5: ...the unit The F070 A has been designed to be implemented in many types of applications For that reason a SETUP level is available to configure your F070 A according to your specific requirements It in...

Page 6: ...apter describes the daily use of the F070 A This instruction is meant for users operators 2 2 CONTROL PANEL The following keys are available Fig 2 Control Panel Functions of the keys This key is used...

Page 7: ...be displayed alternating with the bottom line information When is shown then the value is too high to be displayed Piegraph indication This 10 segment Piegraph gives a quick impression about the actu...

Page 8: ...manual are to be observed Ensure that the measuring system is correctly wired up according to the wiring diagrams The housing may only be opened by trained personnel Take careful notice of the Safety...

Page 9: ...low the word SETUP at the bottom of the display The number is a combination of two figures The first figure indicates the function group and the second figure the sub function Additionally each functi...

Page 10: ...to select in the other direction When data is altered but ENTER is not pressed then the alteration can still be cancelled by waiting for 20 seconds or by pressing ENTER for three seconds the PROG proc...

Page 11: ...999 unit 24 OFFSET 99 999 to 199 999 unit 3 DISPLAY 31 UNDER height percentage off level 32 TOP level height percentage 33 BARGRAPH off on 34 BACKLIGHT optional off green amber 35 BL BRIGHTNESS 1 5 4...

Page 12: ...he selected measurement unit at 20mA The more accurate the span the more accurate the functioning of the system will be Example 1 Calculating the span for level Let us assume that the sensor generates...

Page 13: ...be selected 00000 1111 1 222 22 SPAN 23 With the span the sensor signal is converted to a height The span for height is determined on the basis of the selected measurement unit at 20mA The more accura...

Page 14: ...able measurement over a long period of time The F070 A has several smart power management functions to extend the battery life time significantly Two of these functions can be set LCD NEW 41 The calcu...

Page 15: ...75 INFLUENCE 90 INFLUENCE 99 INFLUENCE 01 filter disabled filter disabled filter disabled filter disabled 02 0 3 seconds 0 5 seconds 1 0 seconds 1 8 seconds 03 0 5 seconds 1 0 seconds 1 5 seconds 3 s...

Page 16: ...f the system After pressing PROG three settings can be selected CALIBRATE with this setting the input will be calibrated with the actual 20mA value After pressing enter CAL SET will be displayed as so...

Page 17: ...ccidental contact is no longer assured when the housing cover is removed or the panel cabinet has been opened danger from electrical shock The housing may only be opened by trained personnel Take care...

Page 18: ...G9 PG9 30mm 30mm 22 5mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30mm 30mm 22 50mm M20 x 1 5 22 5mm M20 x 1 5 M20 x 1 5 25mm 25mm 22 5mm 1 2 NPT 0 9 3x 1 2 NPT 0 12 0 12 0 9 HA HM HN HO HP HT HU 6 x M12 12mm 12m...

Page 19: ...K HK back box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 20mm D 20mm D 16mm HC 75 mm 2 95 118 mm 4 65 104...

Page 20: ...plied with the 115 230V AC power supply type PM The green yellow wire between the back casing and removable terminal block may never be removed Fig 7 Grounding aluminum enclosure with type PM 115 230V...

Page 21: ...t isolated The screen of the signal wire must be connected to the common ground terminal Terminals 1 2 sensor INPUT LOOP POWERED type A PL Model F070 A PL is powered from the 4 20mA sensor signal In t...

Page 22: ...omatically to extend the battery life time The input loop powered model type F070 A PL does not have this power supply option Terminal 6 sensor supply voltage type PD With this option a sensor supply...

Page 23: ...sure Warning be sure that all the leads to the terminals are disconnected from the unit when the internal plastic protection cover has been removed HIGH VOLTAGE 400V NEVER connect the mains power supp...

Page 24: ...24V max 400mA 24V DC EARTH AC AC Note PF PM The total consumption of the sensor and backlight type ZB may not exceed 400mA 24V DC Terminals 5 7 Sensor input The F070 A requires a 0 4 20mA sensor sign...

Page 25: ...ct certificate KEMA 05ATEX1168 X For installation under IECEx scheme this intrinsically safe device must be installed in accordance the product certificate IECEx KEM 08 0006X For installation under CS...

Page 26: ...461 FM Project ID 3033306 40 C 70 C 40 F 158 F Fig 12 Label information Intrinsically Safe application Label information analog input loop powered type A PL inside and outside the enclosure Made in Ve...

Page 27: ...mple Intrinsically Safe 5 POWER SUPPLY UNIT TYPE PD PX 6 1 2 SENSOR SIGNAL ANALOG INPUT TYPE A 0 4 20mA 10 POWER SUPPLY BACKLIGHT OPTION ZB SENSOR SUPPLY TYPE PD 4 9 I Configuration example IIA IIB an...

Page 28: ...C PL will power the unit the battery will be disabled automatically till power is disconnected I S level sensor input type A PL 4 20mA loop powered Configuration example IIA IIB and IIC application F0...

Page 29: ...F or expose contents to water INSTRUCTION SHEET BATTERY REPLACEMENT FW LiBAT 001 Replacement Instructions Safety Instructions Fluidwell bv The Netherlands www fluidwell com sales fluidwell com FW LiB...

Page 30: ...above 90 annual mean It is the users responsibility to take all precautions to dehumidify the internal atmosphere of the F070 A in such a way that no condensation will occur for example by placing dr...

Page 31: ...e HH Type HK ABS enclosure Type HS Dimensions 130 x 120 x 75mm 5 10 x 4 72 x 2 95 LxHxD IP67 NEMA4X Drilling 2x PG9 1x M20 Drilling 2x M16 1x M20 Drilling 1x M20 Drilling 2x M20 Drilling 6x M12 Drilli...

Page 32: ...FM approval IS Class I II III Division 1 Groups A to G T4 Class I zone 0 AEx ia IIC T4 Explosion proof Type XF ATEX approval ref EX II 2 GD EEx d IIB T5 Weight appr 15kg Dimensions of enclosure 350 x...

Page 33: ...segment display related to the input signal Level Digits 5 digits Units L m3 GAL USGAL KG lb bbl no unit Decimals 0 1 2 or 3 Height Digits 5 digits Units mm cm m mtr inch ft mmwk mmwc cmwk cmwc mwk mw...

Page 34: ...e pass code is unknown If the pass code is not 1234 there is only one possibility left call your supplier ALARM When the alarm flag starts to blink an internal alarm condition has occurred Press the s...

Page 35: ...technical specification 31 terminal connectors 21 23 version software 16 voltage selection sensor supply 23 LIST OF FIGURES IN THIS MANUAL Fig 1 Typical application for the F070 A 5 Fig 2 Control Pane...

Page 36: ...LCD new 1 sec 42 mode operational 5 SENSOR 51 filter 01 off 52 cut off 00 0 53 calibrat low 0 4mA default 54 calibrat high 20mA default 6 OTHERS 61 model F070 A F070 A F070 A 62 software version 03 __...

Reviews: