Power Logger
Measuring
Functions
35
This measuring mode records the voltage of every phase (L
1
, L
2
, L
3
) in cases of
voltage dips, swells or interruptions (recorder function).
This function exclusively works with the recorder function.
Before you start the measurement, select the desired threshold value with
Menu/Esc
(under recording adjustments). After the measurement has started
the following message appears on the display.
. . . waiting for events
The Logger is now in the trigger mode. If an event on one of the phases occurs,
the recording is started automatically and lasts for 4 minutes. The MIN and
MAX values of the half-cycle RMS values are shown as waves. The
screenshots recorded by this method are saved as individual pictures and can
be viewed later, or the data can be displayed with the
Power Log
software. A
total of 999 events can be recorded. In the LC display the phase and the
number of recordings are displayed.
edx029.bmp
21
Switch between the individual events (if there is more than one).
This is also possible if the recording has been stopped and you want to
evaluate the stored events.
With
Hold/Run
you can stop/start the measurement or you can also start a new
measurement.