1744/1743
Users Manual
52
General Specifications
RMS Logging Slow Voltage Variations
Logging values: Mean value
RMS values averaged over interval length
Min, Max values
Averaging with selectable averaging time from
0.5 periods to 5 s
Max value
Max 10 ms RMS value per interval
Min value:
Min 10 ms RMS value per interval
Current Logging Values
Mean value
RMS values averaged over interval length
Max value
Highest RMS value per interval
Events Dips, Swells, Interruptions
Limit value
Variable
Lower limit: 0 to 95% V
N
Upper limit: 105 to 120% V
N
Set in PQ Log
Range
0 to V
I
+ 20%
Logging value
½ period RMS value
Operating uncertainty
< 2% of V
I
Response time
½ line power period
Flicker
Logging value
Flicker severity (Pst / Plt) according to
IEC 61000-4-15
Intrinsic uncertainty Pst
< 5% of m. v
Measuring range Pst
0.4 to 4