1745
Users Manual
50
Logging Function Parameters
Logging Values
Voltage L1 or A, L2 or B, L3 or C: phase-phase or phase-neutral:
•
Voltage (mean, max, min values)
•
Voltage harmonics 1
st
to 50
th
order (Logging Function A only)
•
THDV (harmonic contents of voltage)
•
Interharmonics 5 to 2500 Hz (in steps of 0.5 Hz) (Logging Function A
only)
•
Flicker P
st
,P
lt
•
Unbalance
•
Signaling voltages
•
Frequency
•
Voltage events (dips, swells, interruptions)
Current L1 or A, L2 or B, L3 or C, and N:
•
Current (mean, max values)
•
Harmonics of phase and neutral currents up to 50
th
order (Logging
Function A only)
•
Crest factor and peak values of the currents
Power:
•
Active power P (mean, min, and max values)
•
Absolute values active power |P| (mean, min, and max values)
•
Distorting power D (mean, min, and max values)
•
Apparent power S (mean, min, and max values)
•
Power Factor PF, tangent
•
Energy per averaging interval
Total power:
•
Total power P, |P|, D, S
•
3-wattmeter method
•
2-wattmeter method (Aron circuitry)
•
2 ½ wattmeter method
Shop for Fluke products online at:
1.877.766.5412
www.
MyFlukeStore
.com
Summary of Contents for 1745-BASIC
Page 12: ...1745 Users Manual iv Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...
Page 14: ...1745 Users Manual vi Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...
Page 72: ...1745 Users Manual 58 Shop for Fluke products online at 1 877 766 5412 www MyFlukeStore com ...