Logging
When the Logger is connected and ready, you can perform three types of
logging:
Switch-activated job
: The status LED is blinking. Press the
START/STOP button once. As soon as the job is active, the LED is
on continuously. If needed, the job can be cancelled after running for
at least one minute, and restarted later.
Time-activated job
: The Logger starts logging as soon as the pre-
programmed start time is reached and stops at the defined end time.
Immediate job
: The Logger starts logging as soon as power is on.
Note the following about logging jobs:
1.
The connection can be verified with the LCD (voltage, current,
power). If all three LEDs are lit continuously, the voltage connections
and signal levels are within nominal range. For details, see Table 4 in
the
Features
section.
2.
The Logging job status is indicated by the status LED. For details, see
Table 4 in the
Features
section.
Completing the Logging Job
1.
Terminate the job as follows:
•
For switch activated jobs
: At the end of the logging period,
stop the logging job by pressing the START/STOP button.
•
For time activated and immediate jobs
: Stop the job in PQ
Log with the
icon, or with menu Logger/Stop logging
Note
Make sure the logging job is stopped with the START/STOP button
(switch activated jobs) or PQ Log (time activated jobs) before the
terst leads or power supply leads are removed. Otherwise, the Logger
will record a voltage interruption.
Only switch-activated jobs can be aborted. Time activated jobs are
terminated only when the programmed measuring time has elapsed.
Summary of Contents for 1745