Power Quality Logger
Technical
Specifications
49
Power P, S, |P|
Active power P
As per EN 61036, class 2
Distorting power D
As per EN 61268, class 2 (A-version only)
Max value
Highest value per interval
Min value
Smallest value per interval
Phase uncertainty
< 0.3 degrees
Conditions Conductor
centered
within clamp jaws or
Flexi Set.
Harmonics (Logging Function A Only)
V
m
, I
m
, THDV, THDI per IEC/EN 61000-4-7, class B
Voltage harmonics (function A)
intrinsic uncertainty:
For V
m
< 3 % V
N
: < 0.15 % V
N
For V
m
≥
3 % V
N
: < 5 % V
m
Current harmonics (function A)
Intrinsic uncertaintyi
For I
m
< 10 % I
N
: < 0.5 % I
N
For I
m
≥
10 % I
N
: < 5 % I
m
THD V (function A) intrinsic
uncertainty at V
N
For THD V < 3 %: < 0.15 %
For THD V
≥
3 %: < 5 %
THD V (function P) intrinsic
uncertainty at V
N
For THD V < 3 %: < 1 %
For THD
≥
3 %: < 5 %
THD I (functions A, P) intrinsic
uncertainty at I
I
For THD I < 3 %: < 2 %
For THD I
≥
3 %: < 5 %
Statistics
Frequency
42 classes for 10 s mean values
Ripple-control signals.
Interharmonics
21 classes for 3 s mean values.
Analysis of logging data
Programming and analysis is done by PQ Log software on PC.
Summary of Contents for 1745
Page 12: ...1745 Users Manual iv ...
Page 14: ...1745 Users Manual vi ...
Page 72: ...1745 Users Manual 58 ...