C3531
Voltage range
Standard drive units
Explosion-proof drive
units
Maximum number of
starts per hour
Up to 1.1 kV
705
715
15
735
745
15
765
775
15
805
815
15
835
845
15
865
875
15
885
895
8
905
915
8
935
945
8
965
975
8
1.2-6.6 kV
862
872
15
882
892
8
950
960
8
985
995
8
C3602
Voltage range
Standard drive units
Explosion-proof drive
units
Maximum number of
starts per hour
Up to 1.1 kV
735
745
15
765
775
15
805
815
15
835
845
15
865
875
15
885
895
8
905
915
8
935
945
8
1.2-6.6 kV
862
872
15
882
892
8
950
960
8
985
995
8
C3800
Voltage range
Standard drive units
Explosion-proof drive
units
Maximum number of
starts per hour
Up to 1.1 kV
905
915
8
935
945
8
965
975
8
1.2-6.6 kV
950
960
8
985
995
8
Operational data
Application limits
Table 40: Process data
Parameter
Value
Liquid temperature
Max. +40°C (+105°F)
Depth of immersion
Max. 20 m (65 ft.)
pH of pumped liquid
pH 6–11
Liquid density
Max. 1100 kg/m
3
(9.17 lb per gal.)
Technical Reference
110
C3300/6x5, C/R3231, C3240, C3306, C3312, C3351, C3356, C3400, C3501, C3531, C3602, C3800 Installation,
Operation and Maintenance Manual