4-79
03-1X=0
: During Running
ON: Run command is ON or output frequency is greater than 0
OFF: Run command is OFF and the AC Drive is stopped.
03-1X=1
: Fault contact output
Output is active during fault condition. Communication error (CF00, CF01) does not activate the fault contact.
03-1X=2
: Frequency Agree
Output is active when output frequency falls within frequency reference minus the frequency detection width (03-14).
03-1X=3
: Setting Frequency Agree
Output is active when the output frequency falls within the frequency detection width (03-14) of the set frequency
detection level (03-13).
03-1X=4
: Frequency detection 1
Output is active when the output frequency rises above the frequency detection level (03-13) + frequency detection
width (03-14) and deactivates when the output frequency falls below frequency detection level (03-13).
03-1X=5
: Frequency detection 2
Output is active when the output frequency is below the frequency detection level (03-13) + frequency detection width
(03-14) and turns off when the output frequency falls below frequency detection level.
Refer to “Functions of Multi-function Digital Output” table for the operation of frequency detection.
03-1X=6
: Automatic restart.
Output is active during an auto-restart operation.
03-1X=7
: Momentary AC power loss
Output is active during a momentary AC power loss
03-1X=8
: Rapid Stop
Output is active during a rapid stop
03-1X=9
: Baseblock (B.B.)
Output is active when the AC Drive output is turned off during a Baseblock command.
03-1X=10
: Motor Overload Protection (OL1)
Output is active during motor overload detection (OL1)
03-1X=11
: Drive Overload Protection (OL2)
Output is active during AC Drive overload detection (OL2)
03-1X=12
: Over torque threshold level (OC3)
Output is active during an over torque detection see parameters 08-13 – 08-16.
03-1X=13
: Preset Output Current Reached
When output current > 03-15 for duration > 03-16, output is ON.
03-1X=14
: Brake control
Output is active when brake control is active
03-1X=15
: PID feedback signal loss
Output is active when PID feedback signal is lost (e.g. wire break)
03-1X=16
: Single pre-set count
03-1X=17
: Dual pre-set count
03-1X=18
: PLC status (setting =18)
Output is active when operation command parameter (00-02) is set to 3: PLC Control.