Group 01 Basic Motor Parameters
Param.
#
Parameter Name
Setting Range
Default
Unit
Control Mode
Notes
V/F
SLV
PM/SLV
01-00
V/F Curve Motor 1
0–FF
F
-
X
X
*3, (Note)
01-02
Maximum Output Frequency Motor 1
4.8–599.0
50.0/60.0
Hz
*8
01-03
Maximum Output Voltage Motor 1
240V: 0.1–255.0
230
V
X
X
*8
480V: 0.2–510.0
460
01-04
Middle Output Frequency 2 Motor 1
0.1–599.0
0
Hz
X
X
(Note)
01-05
Middle Output Voltage 2 Motor 1
240V: 0.0–255.0
0
V
X
X
*8, (Note)
480V: 0.0–510.0
01-06
Middle Output Frequency 1 Motor 1
0.1–599.0
3
Hz
X
X
(Note)
01-07
Middle Output Voltage 1 Motor 1
240V: 0.0–255.0
KVA
V
X
X
*8, (Note)
480V: 0.0–510.0
01-08
Minimum Output Frequency Motor 1
0.1–599.0
V/F:
KVA
Hz
(Note)
SLV:
0.6
PMSLV:
10
01-09
Minimum Output Voltage Motor 1
240V: 0.0–255.0
KVA
V
X
X
*8
480V: 0.0–510.0
01-10
Torque Compensation Gain
0–10.0
0.5
-
X
X
*1
01-11
Torque Compensation Mode
0: Mode 0 (Normal)
0
-
X
X
1: Mode 1 (High Speed)
01-12
Nameplate Frequency of Motor 1
4.8–599.0
50.0/60.0
Hz
X
*8
01-13
Base (Nameplate) Output Voltage
Motor 1
240V: 0.0–255.0
230
V
X
X
*8
480V: 0.0–510.0
460
01-14
Input Voltage Setting
240V: 55.0–255.0
230
V
*8
480V: 10.0–510.0
460
01-15
Torque Compensation Time
0–10000
200
ms
X
X
01-16
Maximum Output Frequency Motor 2
4.8–599.0
50.0/60.0
Hz
X
X
*8
01-17
Maximum Output Voltage Motor 2
240V: 0.1–255.0
230
V
X
X
*8
480V: 0.2–510.0
460
01-18
Middle Output Frequency 2 Motor 2
0.0–599.0
0
Hz
X
X
01-19
Middle Output Voltage 2 Motor 2
240V: 0.0–255.0
0
V
X
X
480V: 0.0–510.0
01-20
Middle Output Frequency 1 Motor 2
0.0–599.0
3
Hz
X
X
01-21
Middle Output Voltage 1 Motor 2
240V: 0.0–255.0
KVA
V
X
X
480V: 0.0–510.0
01-22
Minimum Output Frequency Motor 2
0.0–599.0
1.5
Hz
X
X
01-23
Minimum Output Voltage Motor 2
240V: 0.0–255.0
KVA
V
X
X
480V: 0.0–510.0
01-24
Nameplate Frequency Motor 2
4.8–599.0
50.0/60.0
Hz
X
X
*8
01-25
Base (Nameplate) Output Voltage
Motor 2
240V: 0.0–255.0
230
V
X
X
*8
480V: 0.0–510.0
460
01-26
V/F Curve Motor 2
0–FF
F
-
X
X
*3
01-00
:
When editing using the LED keypad, display shows H00XX indicating the value is to be input as a hexadecimal.
01-04 to 01-07 and 01-18 to 01-21:
Values are only editable when 01-00=F or FF
*1:
Parameter can be changed while running.
*3:
Parameter will not reset to default during a factory reset (initialization).
*8:
Parameter value / default setting is dependent on drive size / model