4-35
Group 16 LCD Keypad Parameters
Param.
#
Parameters
Setting Range
Default
Unit
Control Mode
Notes
V/F
SLV
PMSLV
16-00
Main Screen Monitoring
5–39 when using LCD to operate, the
monitored item displays in the first line.
(default is frequency command)
16
-
*1
16-01
Sub-Screen Monitoring 1
5–39 when using LCD to operate, the
monitored item displays in the second
line. (default is output frequency)
17
-
*1
16-02
Sub-Screen Monitoring 2
5–39 when using LCD to operate, the
monitored item displays in the third line.
(default is output current))
18
-
*1
16-03
Display Unit
0–39999:
Determine the display way and unit of
frequency commands
0: Frequency display unit is 0.01Hz
1: Frequency display unit is 0.01%
2: Frequency display unit is rpm.
3–39: Reserved
40–9999:
Users specify the format, Input 0XXXX
represents display of XXXX at 100%.
10001–19999:
Users specify the format Input 1XXXX
represents display of XXX.X at 100%.
20001–29999:
Users specify the format, Input 2XXXX
represents display of XX.XX at 100%.
30001–39999:
Users specify the format, Input 3XXXX
represents display of X.XXX at 100%.
0
-
16-04
Engineering Unit
0: Without using engineering units
1: FPM
2: CFM
3: PSI
4: GPH
5: GPM
6: IN
7: FT
8: /s
9: /m
10: /h
11: °F
12: inW
13: HP
14: m/s
15: MPM
16: CMM
17: W
18: KW
19: m
20: °C
21: RPM
22: Bar
23: Pa
24: KPa
0
-