FUEL BED LAYOUT

Please see the relevant section of the user instructions.

FITTING THE FIREFRONT 

Place the decorative firefront in front of the fire and slide the ashpan door into place. The firefront shown in these instructions may be dif-
ferent to the one supplied with the appliance.

GAS CONNECTION

Purge the gas supply thoroughly to remove air and dirt/debris BEFORE connection. Now disconnect the inlet restrictor elbow from the inlet
pipe. Connect the previously installed gas supply to inlet restrictor elbow, and re-fit the restrictor elbow to the inlet pipe of the appliance.
If using an across hearth connection, ensure the decorative fireframe and firefront will clear the supply route.
If the data/control plate is not already fitted, attach with two screws, ensuring the control knob is free to be depressed fully.

TESTING AND COMMISSIONING

Turn on and test the gas supply up to the fire for any leaks, in accordance with current edition of BS6891.
When the appliance is first used, protective oils coating the firebox may burn off. It is advisable to ventilate the room during this period for
at least one hour.

OPERATING THE APPLIANCE 

The pilot is visible through the left hand side of the matrix. Rotate the coals for good viewing. Push
in and turn the control knob to the SPARK position, and hold there for a few seconds.

Continue turning anti-clockwise through the spark click to the PILOT light position, ensuring the
pilot has lit. If not, return the knob clockwise, and repeat.

When the pilot lights after the spark, keep the knob depressed for approximately ten seconds.
Now release the knob and the pilot should stay alight. If the pilot is extinguished during use, wait
three minutes before repeating the ignition procedure. 

To achieve the HIGH setting, push the control knob in slightly and continue turning anti-clockwise
to the high position. The main burner should light after a few seconds. 

To decrease the setting to LOW, turn the control knob clockwise to the low setting.

To turn to the PILOT position from the HIGH or LOW positions, press the control knob in, and return to the pilot position and release. To turn
the fire OFF, keep the knob pressed in, return to the off position and release.

SPARK FAILURE

The gap between the spark electrode and the pilot should be 3.5 - 4.5mm to produce a good spark. There should be no need to adjust this.
If under any circumstances the electric spark fails, the pilot may be lit manually by proceeding with the ignition sequence as previously
described, and after turning the control knob through the spark position, the knob should be held in and the pilot lit with a taper.

SETTING PRESSURE

Remove the screw from the pressure test point. 

The ttest ppoint  iis ssituated oon tthe m

main iinjector ppipe  

Attach a U gauge. Light the fire on the HIGH setting. The setting pressure should
be in accordance with the figures stated on page 2 of these instructions. The fire
is factory set to achieve these pressures, and any significant variation could indi-
cate a supply problem.

If the pressure is too high, the gas supply meter may be set incorrectly. This should
be checked with the fire running and if necessary reset by the gas supplier. If the
pressure is too low, then check the meter governor pressure with the appliance
running. If this is incorrect it will need to be reset by the gas supplier.

If the setting pressure is too low, but the meter pressure is acceptable, then a prob-
lem in the supply pipework is to be suspected. This will be dirt and debris, kinked or inadequate size pipes, restriction in a fitting or solder
flashing across a joint. (NOTE: you will not get an accurate reading of the inlet pressure with a pressure gauge on the end of the supply pipe
- this is the static pressure in the system. You must use a T piece and measure the supply pressure with the fire on High - the dynamic pres-
sure). Refit and tighten the screw into the pressure test point when the test is complete.

FLUE SPILLAGE MONITORING SYSTEM

This fire is fitted with a flue spillage safety device (ODS). If the fire shuts down during use for no apparent reason then several things may be
suspected. If a door or window has been opened creating a draught, then pilot disturbance is the problem, and removal of the draught should
resolve this. The gas pressure reaching the fire must also be checked (again, recall your installer to check and rectify any problem). The ther-
mocouple connection into the back of the gas control valve may also have worked loose during installation, simply get the installer to tight-
en. If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the appliance OFF, check the flue and carry
out any remedial work required. Relight the fire and carry out a spillage test. DO NOT allow the appliance to be used if it continues to fail a
spillage test.

8

12.0

13.0

13.1

14.0

14.1

14.2

14.3

14.4

Summary of Contents for 18" High-Tech

Page 1: ......

Page 2: ...y a competent person in accordance with Gas Safety Installation and Use Regulations 1998 It is strongly recommended that a CORGI registered engineer be used for this purpose Read all these instructions before commencing installation This appliance must be installed in accordance with the rules in force and only used in a sufficiently ventilated space The appliance is designed for installation on t...

Page 3: ...tions s b before i ins stallation a and u us se o of t this s a applianc ce This s a applianc ce i is s f free f from a any a as sbes stos s m material R Refrac ctories s a and c coal b bed a are c cons struc cted f from c ceramic c f fibre 1 Sec ction 1 0 2 0 3 0 4 0 4 1 5 0 6 0 7 0 7 1 8 0 8 1 9 0 10 0 Contents s Important Notes Appliance Data Installation Requirements Site Requirements Debris C...

Page 4: ... before installation by using a smoke pellet or similar to ensure proper draw and that leakage is not evident at any joints Repair and re test as necessary before the appliance is installed The flue must be connected to only one fireplace and the flue must not vent more than one appliance i e not shared with a gas back boiler There must be no opening in the flue apart from the one that the applian...

Page 5: ... the products of combustion to be cleared properly up the flue the outlet at the back of the appliance must have a 50mm mini mum clearance between it and the back wall of the opening or any other obstruction The area immediately above the outlet must form a smooth path into the flue Any type of fire surround used with this appliance must be adequately sealed to the wall and floor A combustible she...

Page 6: ...and any other rules in force PREFABRICATED F FLUE B BOXES This appliance can be fitted into a number of proprietary flue boxes provided that the minimum dimensions given in the diagram below are complied with Constructional N Note The frame of the fire any back panel or other infill panels and the flue box must be sealed together so that there is no possibility of leakage between them Adequate cle...

Page 7: ...e panels should be fitted by inserting their front edges into the pre fitted retaining brackets on the front face of the firebox Gently align the side panels with the side of the firebox as shown over the top of the back panel already in place Make sure that the side panels are pushed up firmly to the roof of the firebox and back firmly to retain the tapered panel Secure both side panels and the l...

Page 8: ...Ensure that it slides in correctly the sealing face sits flat and square to the wall or infill panel and that the base is firm on the floor of the opening as no leaks are permissible here At this stage it is essential to ensure that the spigot outlet of the fire is not restricted in any way Remove the firebox and take any necessary measurements before making good and preparing for final installati...

Page 9: ...the exact layout given the eyebolts should be posi tioned as close to the correct layout as possible Before finally fitting cables ensure the self adhesive sealing strips are in position on the back of the appliance frame The fireframe must be sealed evenly to the fireplace opening all around the periphery Thread the tensioning cables through the holes in the top of the firebox then the eyelets an...

Page 10: ...to adjust this If under any circumstances the electric spark fails the pilot may be lit manually by proceeding with the ignition sequence as previously described and after turning the control knob through the spark position the knob should be held in and the pilot lit with a taper SETTING PRESSURE Remove the screw from the pressure test point The t test p point i is s situated o on t the m main i ...

Page 11: ...d and other superficial damage to the matt black paintwork of the appliance can be covered with matching heatproof spray Use only the manufacturers recommended spray paint Paint only when the fire is OFF and cold Always mask off the surrounding area to pre vent contamination with overspray Ventilate the room during the use of the spray DO NOT attempt to spray paint the coals or ceramics or wash th...

Page 12: ...w through the supporting leg and lift assembly clear The injector pipe can now be checked for debris Remove the nut retaining the injector elbow Blow through the elbow to remove any debris The valve is not field serviceable apart from the pilot filter Remove the control knob by pulling it forwards then remove the largest of the three screws on the face of the valve Slide the filter out and clean a...

Page 13: ...s f for a a t time a and t then c cuts o off Excessive room draught or flue pull rectify Loose or faulty thermocouple rectify ODS system in operation Firebox grommet seal not fitted rectify Lint in pilot aeration hole clean thoroughly internally Pilot f flame s shrinks w when f fire i is o on h high Poor gas flow to fire check pressure with fire on high If pressure is low remove any restriction in...

Page 14: ...r may discolour if fitted too close to the fire See relevant section for further details on clearances to combustibles No combustible material or flooring should protrude onto the hearth DO NOT burn any foreign material on this fire the coals must be of the correct type and laid out in accordance with the relevant section of these instructions Failure to do so could create a hazard or lead to soot...

Page 15: ...ided v ventilation o of a at l least 8 8 75cm2 The requirements of other appliances operating in the same space or room and the results of a spillage test must be taken into consideration when assessing ventilation requirements this will have been car ried out by your CORGI registered installer For Republic of Ireland ventilation may be required see IS 813 ICP3 IS 327 and any other rules in force ...

Page 16: ...matrix Do not place the coals directly over the holes in the matrix The coals may be rotated as desired to ensure they sit firmly on the various supporting parts of the matrix 6 Finally take the five remaining coals and position as shown These coals should rest on the front and rear rows of coals rather than sitting directly on the matrix Adding these coals should complete the appearance of the fu...

Page 17: ... suspected If a door or window has been opened creating a draught then pilot disturbance could be the problem and removal of the draught should resolve this The fire can then be re lit in accordance with the previous section A grommet seal may also be missing from the firebox causing abnormal draught to shut down the pilot Call your installer to check seals are properly fitted If pilot disturbance...