76
NOMINAL DATA
-
750
780
810
870
900
Type of installation
-
C13-C33-C43-C53-C63-C83-C93-C13X-C33X-C43X-C63X-C93X-
B23-B23P-C(10)-C(11)
Nominal heat input Qn
kW
700
740
765
815
840
Nominal heat output (80 – 60 °C) Pn
kW
681,5
720,6
744,9
793,5
817,8
Nominal heat output (50 – 30 °C) Pn
kW
743,5
785,4
812,1
865,5
892,2
Reduced heat input Qr
kW
22,5
11,5
11,5
11,5
22,5
Reduced heat output (80 – 60 °C) Pr
kW
21,6
11,1
11,1
11,1
21,6
Reduced heat output (50 – 30 °C) Pr
kW
23,9
12,4
12,4
12,4
23,9
Efficiency at 100% (80 – 60 °C)
%
97,3
97,4
97,4
97,3
97,3
Efficiency at 100% (50 – 30 °C)
%
106,2
106,1
106,2
106,2
106,2
Efficiency at 30% Qn - 30 °C Return
%
108,4
108,5
108,5
108,4
108,4
Efficiency at reduced heat input (80 – 60 ° C)
%
96
96,2
96,2
96,2
96
Efficiency at reduced heat input (50 – 30 ° C)
%
106,3
108,2
108,2
108,2
106,3
Central heating setting range
°C
20 ÷ 80
CH maximum temperature
°C
80 + 3
Exchanger maximum temperature (TMS)
°C
110
NOx class (EN 15502-1:2012+A1:2015)
1..6
6
6
6
6
6
Heating water max hydraulic pressure (PMS)
bar
6
6
6
6
6
Safety valve calibration pressure
bar
5
5
5
5
5
Heating water minimum pressure
bar
0,8
0,8
0,8
0,8
0,8
DHW temperature setting range
°C
65 ÷ 35
DHW maximum temperature
°C
65
Tab. 22 Nominal data for configurations from 750 to 900
1.16 Nominal electrical data tables
NOMINAL ELECTRICAL DATA
-
45
60
85
90
105
Input voltage
V
230
Frequency
Hz
50
Module power consumption
W
94
119
156
188
213
Module power consumption in standby condition
W
2
2
3,5
4
4
Degree of electrical protection of rack modules
IP
X4D
Tab. 23 Nominal electrical data for configurations from 45 to 105
NOMINAL ELECTRICAL DATA
-
120
150
170
205
240
270
300
Input voltage
V
230
Frequency
Hz
50
Module power consumption
W
251
310
312
407
502
561
620
Module power consumption in standby condition
W
3,5
3,5
7
7
7
7
7
Degree of electrical protection of rack modules
IP
X4D
Tab. 24 Nominal electrical data for configurations from 120 to 300
NOMINAL ELECTRICAL DATA
-
325
360
390
420
450
480
510
Input voltage
V
230
Frequency
Hz
50
Module power consumption
W
658
753
812
871
930
1004
1063
Module power consumption in standby condition
W
10,5
10,5
10,5
10,5
10,5
14
14
Degree of electrical protection of rack modules
IP
X4D
Tab. 25 Nominal electrical data for configurations from 325 to 510