80
1.18
Tables of flue - shared collector dimensioning
FLUE - SHARED COLLECTOR DIMENSIONING
-
45
60
85
90
105
Drain rating
-
B23P
Qn - CO2
%
9,2
9,1
9
9,2
9,1
Qn - Flue gas temperature - Air temperature
°C
57
57,0
45,3
57
57
Qn - Flue mass flow
g/sec
19
27,3
37,2
38
46,2
Qn - Residual head available
Pa
30
30
30
30
30
Qr - CO2
%
8,9
8,9
9
8,9
8,9
Qr - Flue gas temperature - Air temperature
°C
42
39
31,2
42
39
Qr - Flue mass flow
g/sec
1,9
2,8
4,1
1,9
1,9
Qr - Residual head available
Pa
5
5
5
5
5
Connection diameter to flue gas collector
mm
160
160
160
160
160
Tab. 33 Flue - shared collector dimensioning for configurations from 45 to 105
FLUE - SHARED COLLECTOR DIMENSIONING
-
120
150
170
205
240
270
300
Drain rating
-
B23P
Qn - CO2
%
9
9
9
9
9
9
9
Qn - Flue gas temperature - Air temperature
°C
54,0
52,6
45,3
50,4
54,0
53,2
52,6
Qn - Flue mass flow
g/sec
52,7
64,2
74,4
89,9
105,4
116,9
128,4
Qn - Residual head available
Pa
30
30
30
30
30
30
30
Qr - CO2
%
9
9
9
9
9
9
9
Qr - Flue gas temperature - Air temperature
°C
35,4
35,4
31,2
31,2
35,4
35,4
35,4
Qr - Flue mass flow
g/sec
5,3
10,3
4,1
4,1
5,3
5,3
10,3
Qr - Residual head available
Pa
5
10
5
5
5
5
10
Connection diameter to flue gas collector
mm
160
160
160
160
160
160
160
Tab. 34 Flue - shared collector dimensioning for configurations from 120 to 300
FLUE - SHARED COLLECTOR DIMENSIONING
-
325
360
390
420
450
480
510
Drain rating
-
B23P
Qn - CO2
%
9
9
9
9
9
9
9
Qn - Flue gas temperature - Air temperature
°C
51,7
54,0
53,5
53,0
52,6
54,0
53,6
Qn - Flue mass flow
g/sec
142,6
158,1
169,6
181,1
192,6
210,8
222,3
Qn - Residual head available
Pa
30
30
30
30
30
30
30
Qr - CO2
%
9
9
9
9
9
9
9
Qr - Flue gas temperature - Air temperature
°C
31,2
35,4
35,4
35,4
35,4
35,4
35,4
Qr - Flue mass flow
g/sec
4,1
5,3
5,3
5,3
10,3
5,3
5,3
Qr - Residual head available
Pa
5
5
5
5
10
5
5
Connection diameter to flue gas collector
mm
200
200
200
200
200
200
200
Tab. 35 Flue - shared collector dimensioning for configurations from 325 to 510
FLUE - SHARED COLLECTOR DIMENSIONING
-
540
570
600
630
660
690
720
Drain rating
-
B23P
Qn - CO2
%
9
9
9
9
9
9
9
Qn - Flue gas temperature - Air temperature
°C
53,2
52,9
52,6
53,7
53,4
53,1
52,8
Qn - Flue mass flow
g/sec
233,8
245,3
256,8
275
286,5
298
309,5
Qn - Residual head available
Pa
30
30
30
30
30
30
30
Qr - CO2
%
9
9
9
9
9
9
9
Qr - Flue gas temperature - Air temperature
°C
35,4
35,4
35,4
35,4
35,4
35,4
35,4
Qr - Flue mass flow
g/sec
5,3
5,3
10,3
5,3
5,3
5,3
5,3
Qr - Residual head available
Pa
5
5
10
5
5
5
5
Connection diameter to flue gas collector
mm
200
200
200
250
250
250
250
Tab. 36 Flue - shared collector dimensioning for configurations from 540 to 720