81
FLUE - SHARED COLLECTOR DIMENSIONING
-
750
780
810
870
900
Drain rating
-
B23P
Qn - CO2
%
9
9
9
9
9
Qn - Flue gas temperature - Air temperature
°C
52,6
53,5
53,2
52,8
52,6
Qn - Flue mass flow
g/sec
321
339,2
350,7
373,7
385,2
Qn - Residual head available
Pa
30
30
30
30
30
Qr - CO2
%
9
9
9
9
9
Qr - Flue gas temperature - Air temperature
°C
35,4
35,4
35,4
35,4
35,4
Qr - Flue mass flow
g/sec
10,3
5,3
5,3
5,3
10,3
Qr - Residual head available
Pa
10
5
5
5
10
Connection diameter to flue gas collector
mm
250
250
250
250
250
Tab. 37 Flue - shared collector dimensioning for configurations from 750 to 900
1.19 Design data tables
DESIGN DATA
-
45
60
85
90
105
Qn - Casing heat loss with burner on
%
0,15
0,25
0,33
0,15
0,21
Qn - Casing heat loss with burner off
%
0,21
0,17
0,14
0,21
0,19
Qn - Flue system heat loss with burner on
%
2,8
2,65
2,8
2,8
2,71
Qn - Flue system heat loss with burner off
%
---
---
---
---
---
Qn - WILO pump absorption with hydraulic separator
W
75
130
120
150
205
Qn - WILO pump absorption with plate exchanger
W
75
130
120
150
205
Qr - Casing heat loss with burner on
%
1,05
1,06
3,31
1,05
1,05
Qr - Casing heat loss with burner off
%
0,21
0,17
0,141
0,21
0,17
Qr - Flue system heat loss with burner on
%
2,19
1,98
1,87
2,19
1,98
Qr - Flue system heat loss with burner off
%
---
---
---
---
---
Qr - WILO pump absorption with hydraulic separator
W
75
130
120
150
205
Qr - WILO pump absorption with plate exchanger
W
75
130
120
150
205
Tab. 38 Design data for configurations from 45 to 105
DESIGN DATA
-
120
150
170
205
240
270
300
Qn - Casing heat loss with burner on
%
0
0,38
0,33
0,14
0
0,21
0,38
Qn - Casing heat loss with burner off
%
0,08
0,09
0,14
0,11
0,08
0,09
0,09
Qn - Flue system heat loss with burner on
%
2,59
2,27
2,8
2,68
2,59
2,41
2,27
Qn - Flue system heat loss with burner off
%
---
---
---
---
---
---
---
Qn - WILO pump absorption with hydraulic separator
W
260
260
240
380
520
520
520
Qn - WILO pump absorption with plate exchanger
W
260
260
240
380
520
520
520
Qr - Casing heat loss with burner on
%
2,06
2,17
3,31
2,06
2,06
2,06
2,17
Qr - Casing heat loss with burner off
%
0,084
0,09
0,141
0,084
0,084
0,084
0,09
Qr - Flue system heat loss with burner on
%
1,7
1,83
1,87
1,7
1,7
1,7
1,83
Qr - Flue system heat loss with burner off
%
---
---
---
---
---
---
---
Qr - WILO pump absorption with hydraulic separator
W
260
260
240
380
520
520
520
Qr - WILO pump absorption with plate exchanger
W
260
260
240
380
520
520
520
Tab. 39 Design data for configurations from 120 to 300