SSC3100 Operation & Calibration Manual
Description of Calibration Values
11
Spinner Min Output
The Spinner Min Output item sets the duty cycle required to turn the spinner
at its slowest rate. The setting is indicated by having the LIQUID dial
illuminated at 2. The value is indicated illuminating the numbers around
the SPREADER and SPINNER dials. The highest number illuminated
around the SPREADER dial indicates the tens position for the duty cycle
and the highest number illuminated around the SPINNER dial indicates the
ones position. The default value is 20% and is represented by having the
0, 1, and 2 numbers illuminated around the SPREADER dial and the 0
number illuminated around the SPINNER dial.
Use the green SPREADER knob to activate/deactivate the output to test
the spinner speed when adjusting the Min Output value. The ACTIVE LED
will illuminate green when the spreader control is out of standby and
running the output. Rotating the SPREADER knob will increase/decrease
the duty cycle by 10% and using the SPINNER knob will increase/decrease
the duty cycle by 1%.
Spinner Max Output
The Spinner Max Output item sets the duty cycle required to turn the
spinner at its fastest rate. The setting is indicated by having the LIQUID dial
illuminated at 3. The value is indicated by illuminating the numbers around
the SPREADER and SPINNER dials. The highest number illuminated
around the SPREADER dial indicates the tens position for the duty cycle
and the highest number illuminated around the SPINNER dial indicates the
ones position. The default value is 75% and is represented by having the
numbers 0 thru 7 illuminated around the SPREADER dial and the numbers
0 thru 5 illuminated around the SPINNER dial.
Use the green SPREADER knob to activate/deactivate the output to test
the spinner speed when adjusting the Max Output value. The ACTIVE LED
will illuminate green when the spreader control is out of standby and
running the output. Rotating the SPREADER knob will increase/decrease
the duty cycle by 10% and using the SPINNER knob will increase/decrease
the duty cycle by 1%.
Liquid Min Output
The Liquid Min Output item sets the duty cycle required to turn the liquid
pump at its slowest rate. The setting is indicated by having the LIQUID dial
illuminated at 4. The value is indicated illuminating the numbers around
the SPREADER and SPINNER dials. The highest number illuminated
around the SPREADER dial indicates the tens position for the duty cycle
and the highest number illuminated around the SPINNER dial indicates the
ones position. The default value is 20% and is represented by having the
0, 1, and 2 numbers illuminated around the SPREADER dial and the 0
number illuminated around the SPINNER dial.
Summary of Contents for SSC3100
Page 1: ...SSC3100 Operation and Calibration Manual ...
Page 2: ......
Page 4: ......
Page 23: ......
Page 24: ...Document No M0126 B Released 12 30 2019 Copyright 2019 FORCE America Inc ...