LED1 

indicates a correct remote is being received, 

or that you are in limit or remote learning mode. 

 

LED2 

 F

lashes while closing. On when closed

.

 

LED3 

Flashes while opening. On when open 

LED4 

Indicator for input 

[F]

.

 

On when safe. 

LED5 

Indicator for input 

[E]

.

 

On when safe. 

LED6 

Indicator for input 

[G]

.

 

On when active 

LED7 

Indicator for input 

[D]

.

 

On when active

 

LED8 

Indicates the batteries are charging

 

 

Motor checks 

- 3 ohms between blue & brown.

 

 

S

af

ety
 

DIPs 

 

16 

11 

12 

13 

14 

15 

FORCE           %  TIMER           %  LV                   %  RV                  % 

User record 

2   

3   

4   

5   

6   

Input 

Position 

Device 

 

FA31 

 

 

 

 

 

 

Installation record     

complete this table as part of your records

 

Acti

va

tion
 

Input 

Position 

Device / code 

 

 

 

 

 

 

 

 

Fault finding 

 

There are 8 LED’s on RIO-X that show the states 
of inputs and the gate position.  

Gate  runs  slowly 

This happens when there 

has  been  a  loss  of  power.  The  controller  needs 
to re-find it’s limits. This is done automatically. 

 

Gate  will  not  close 

Check LED’s 4&5. They 

should be ON unless a safety device is active. 

 

Randomly  triggers 

There may be a missing 

remote, or loose wiring in 

[G] 

or 

[D]

 . 

 

Gate stops before fully open or closed. 

Can  be  the  stall  detector  has  sensed  an  object. 
Check for stiff or dry hinges. Increase FORCE pot.  

LED3 flashes 4 times 

- cannot find the limit.

 

Gate  will  not  operate 

- Are there any LED’s 

on?  Check  power  in,  battery  voltage  and  fuses. 
Isolate wiring thus; link [E] to [C]. Link [F] to [C]. 
Empty  terminals  [G]  and  [D].  Does  it  now  work 
on remotes?

 

AXEL 

Summary of Contents for AXEL F730

Page 1: ...www forematic com Underground gate opener AXEL AXEL F730 installation...

Page 2: ...nd up to date Technical Specifications Supply volt age 220 240Vac Motor power 100W 24Vdc Supply rating 2 5A 50 60Hz Motor torque 250Nm max Standby power 10W Motor insula tion IP67 Ambient temp 20 to 7...

Page 3: ...compliance that ensure the gate is safe to users and public Automatic gate signs are required on both sides of the gate warning against risk of contact injury The installer must prepare a handover pac...

Page 4: ...s The most common D requires the gate to be off centre and therefore will require a safety edge to protect the pinch hazard E is on centre but leaves a sight gap or you need to cope with a rear hung g...

Page 5: ...ently fill the casement then fill the soakaway Consider a surface drain Wood swells when it absorbs moisture A gap between gate boards and between gate leaves is essential Any sight gap between leaves...

Page 6: ...or with steel post reinforcement That is a decision beyond the scope of this manual Two concrete bases are required for the piers set at precisely the same level Level off 170mm below road level to g...

Page 7: ...ss control it is normally fitted to the left pier because that is the side visitors get out of their vehicles Height is typically 1 5m Leave a suitable duct access hole Ducts will run either to the co...

Page 8: ...you need the gate to open less you can fit an addition ground stop Fit the stub axle plate and stop plate over the exposed studs in the upper shelf then fix with the locking nuts Fig 12b Motor arms M...

Page 9: ...ter the panel through glands Running the cables behind the PCB keeps the limited space tidy It is better to hide cables than cut them too short Mark all cables The wiring plan below shows individual c...

Page 10: ...Move the green wire to D for single leaf door opening Remotes can be set for these two functions See user instructions SAFETY DEVICES F C or E C There two inputs are for safety devices Input F preven...

Page 11: ...o work during the day could be viable free entry device for a commercial property Keypads are useful for friends family or trusted delivery drivers This keypad can accept many codes and some for singl...

Page 12: ...hinge position is on the pier corner so finger traps are less likely Fig21 An safety edge has been added to the gate leaf that closes last There are now two devices on F wired as Fig26 or Fig27 Fig22...

Page 13: ...nd of the gate E or F power Beam Fig 27 One DRI edge on on a pier power Beam Fig 28 Wiring 2 DRI s Yellow NC Blue Com Black Gnd Red Supply power Open Timer A wired switch or timer can hold a gate open...

Page 14: ...y 100 010 110 001 101 011 111 5s 15s 20s 60s 65s 75s 80s Delay 2s 3s 4s 5s DIP 1 2 opening 00 10 01 11 DIP 3 4 closing 00 10 01 11 PCB buttons There are two buttons on the PCB The CODE button is used...

Page 15: ...ial for force test limits The safe force limits need to be observed Adjusting the first 3 settings will help comply The adjustments above should not affect the limit learning Small changes in physical...

Page 16: ...p to maintain safety Our website PICO support page has fault finding support You can save up to 50 remotes There are two remote channels Pedestrian channel opens one gate only Main opens both You will...

Page 17: ...ords Activation Input Position Device code G Fault finding There are 8 LED s on RIO X that show the states of inputs and the gate position Gate runs slowly This happens when there has been a loss of p...

Page 18: ...de of Practice can be found at www dhfonline org uk Force testing EN12445 explains the method of testing the impact forces of a gate The crux is a graph of acceptable forces from the point of impact S...

Page 19: ...of Practice Draw in or Shear Gaps where a body part could be drawn in are not allowed Limbs have different nominal sizes Finger gaps need to be less than 8mm D2 arms less than 100mm etc A solid infil...

Page 20: ...ot accept costs for dismantling installation or for carriage Parts replaced under warranty are the property of the warrantor The warranty period for Radio Equipment is 24 months The period for replace...

Reviews: