The FortiGate unit can be placed on any
flat surface
, or
mounted
in any standard 19 inch
rack unit with the provided
rack-mount brackets
and
screws
.
Please read “Cautions and Warnings” on page 18 prior to installing your device.
To install the FortiGate unit into a rack
1. Ensure that the FortiGate unit is placed on a stable surface
prior to
rack-mount
installation.
2. Attach the provided
rack-mount brackets
to the sides of
the unit using the provided
screws
.
a. If you are installing the unit into a
four-post rack
, attach
the
rack-mount brackets
with the
handles aligned
with the
front
of the FortiGate unit.
b. If you are installing the unit into a
two-post rack
, attach
the
rack-mount brackets
with the
handles aligned
with the
middle
of the FortiGate unit.
11
10
10
11
Caution:
Electrostatic
discharge (ESD)
can damage
your Fortinet
equipment.
Do not place
heavy objects on
the unit.
To avoid personal
injury or damage
to the unit, it is
recommended
that two or more
people install the
unit into the rack.
Note:
If the unit
has a redundant
power supply,
each power
cable should be
connected to a
different power
source. In this
way, if one power
source fails, the
other may still be
operational and
the unit will not
lose power.
1.5in
1.5in
Installation
3
3. Position the FortiGate unit in the
rack
. Ensure there is enough room around the unit to
allow for sufficient air flow.
4. Line up the
rack-mount bracket holes
to the
holes on the rack
and ensure that the
FortiGate unit is level.
5. Finger tighten
four rack-mount screws
to attach the unit to the
rack
.
6. Verify that the spacing around the FortiGate unit conforms to requirements and that
the unit is level, then tighten the
rack-mount screws
with an appropriate
screwdriver
.
7. Using the provided
power cables
, plug the
cables
into the rear of the unit, and then
into
grounded electrical outlets
or a separate power sources, such as
uninterruptible
power supplies
(UPS) or
power distribution units
(PDU).
To install the unit on a flat surface
1. Ensure that the surface onto which the FortiGate unit to be installed is clean, level,
and stable and that there is at least
1.5in
(3.8cm) of clearance on all sides to allow for
adequate airflow.
2. Attach the provided
rubber feet
to the bottom of the FortiGate unit.
3. Place the unit in the designated location.
4. Verify that the spacing around the FortiGate unit conforms to requirements and that
the unit is level.
5. Using the provided
power cables
, plug the
cables
into the rear of the unit, and then
into
grounded electrical outlets
or a separate power sources, such as
uninterruptible
power supplies
(UPS) or
power distribution units
(PDU).