Power connection and configuration
Fortinet Technologies Inc.
Connecting a FortiGate-5144C chassis to ground
Data Center
ground
connector
(Central office
ground system)
Chassis
Ground
Connector
(green)
To connect the FortiGate-5144C chassis to ground
1.
Attach the ESD wrist strap to your wrist and to an ESD socket or to a bare metal surface on the chassis or frame.
2.
Make sure that the chassis and ground wire are not energized.
3.
Connect the green ground wire from the local ground to the ground connector on the FortiGate-5144C chassis.
4.
Secure the ground wire to the chassis.
5.
Optionally label the wire GND.
FortiGate-5053B power supply shelf and PSU-5000B power supplies
If DC power is not available at your location, you can use the FortiGate-5053B 1U 19-inch rack mount power supply
shelf with PSU-5000B hot swappable power supplies to convert AC power to DC power. These components are not
supplied with the FortiGate-5144C chassis and must be purchased separately.
FortiGate-5053B power supply shelf with four PSU-5000B power supplies
PSU-5000B hot swappable
Power Supplies (4)
Edge
Controller
In addition to adding multiple FortiGate-5053B power supply shelves for additional power, you can also pair a FortiGate-
5053B with a FortiGate-5053B-LC power supply shelf. The LC unit can also include up to four PSU but does not include
an edge controller. Instead, both FortiGate-5053B power supply shelves are managed by one edge controller.
FortiGate-5144C 6.2.3 Chassis Guide