Physical description of the FortiGate-5060 chassis
FortiGate-5060 chassis
FortiGate-5060 Chassis Guide
10
01-400-129494-20110912
Physical description of the FortiGate-5060 chassis
The FortiGate-5060 chassis is a 5U chassis that can be installed in a standard 19-inch
rack.
describes the physical characteristics of the FortiGate-5060 chassis.
FortiGate-5060 shelf managers
The FortiGate-5060 chassis includes one or two redundant hot-swappable shelf
managers, located in the dedicated shelf manager slots near the top of the FortiGate-5060
front panel. The primary shelf manager is installed on the left (SM 1) the secondary shelf
manager (if present) is installed on the right (SM 2). The secondary shelf manager is
optional.
The shelf managers support redundant operation with automatic switchover. If both shelf
managers are operating normally, one acts as the active shelf manager and the other as
the standby. Usually the primary shelf manager would be the active shelf manager and the
secondary shelf manager would be the standby shelf manager. The shelf managers
monitor each other and either can trigger a switchover if necessary. The active shelf
manager performs all shelf manager functions. If the active shelf manager fails or is
removed, the standby shelf manager takes over all shelf manager functions.
The FortiGate-5060 shelf managers control chassis power allocation, monitor chassis
operating parameters, monitor and control chassis cooling, and can signal alarms if the
chassis encounters problems. All FortiGate-5000 modules installed in the chassis
communicate with the shelf managers.
Table 1: FortiGate-5060 chassis
physical description
Dimensions
8.75 x 17 x 18.9 in. (22.2 x 43.2 x 48cm) (H x W x D) The
depth is from the fan tray handles on the front panel to the
connectors on the PEMs on the back panel.)
Shipping weight completely
assembled
with packaging
65.7 lb. (30 kg)
Chassis weight completely
assembled with shelf manager
and air baffles (5 front and 6
RTM)
50.7 lb. (23 kg)
Torque Rating
1.2 N m to 1.5 N m
Operating environment
Temperature (long term): 41 to 104°F (+5 to 40°C)
Temperature (short term): 23 to 131°F (-5 to 45°C)
Relative humidity: 5 to 85% (Non-condensing)
Power consumption
Maximum: 350 W (Power consumed by an empty chassis with
two fan trays, 2 shelf managers, one shelf alarm panel and 2
PEMs installed and operating with the fans running at full
speed.)
Power input
2x redundant -40.5 VDC to -60 VDC, 45 A total per PEM
Overcurrent Protection
30 A Fused Switches on PEMs
Cooling Capacity
Front Boards: 300 W per board
RTM: 30 W per module
Protected Earth Test
EN60950-1, test current 25 A, resistance <100mOhm
Hipot Test
EN60950-1, 1000 V