WARNING
: The intra-building ports, Gigabit Ethernet, RJ-45 10/100/1000 Base-T
Ethernet, and RS-232 Serial ports of any FortiGate, FortiSwitch, and FortiController
5000 Series Boards, including Shelf-Manager of the equipment or subassembly is
suitable for connection to intrabuilding or unexposed wiring or cabling only. The intra-
building port(s) of the equipment or subassembly MUST NOT be metallically
connected to interfaces that connect to the OSP or its wiring. These interfaces are
designed for use as intra-building interfaces only (Type 2 or Type 4 ports as described
in GR-1089-CORE, Issue 6) and require isolation from the exposed OSP cabling. The
addition of Primary Protectors is not sufficient protection in order to connect these
interfaces metallically to OSP wiring.
•
FortiGate-5000 series chassis shall be installed and connected to the common
bonding network.
•
FortiGate-5000 series chassis are suitable for installation in the Central Office and
NEC.
•
The battery returns of FortiGate-5000 series chassis shall be connected as DC-I.
•
All bare grounding connection points to FortiGate-5000 series chassis shall be
cleaned and coated with an anti-oxidant solution before connections are made.
•
All surfaces on FortiGate-5000 series chassis that are un-plated shall be brought to a
bright finish and treated with and anti-oxidant solution before connections is made.
•
All non-conductive surfaces on FortiGate-5000 series chassis shall be removed from
all threads and connection points to ensure electrical continuity.
•
Unambiguous reference to service documentation for instructions for replacement of
fuses replaceable only by service personnel.
•
The FortiGate-5140B chassis is capable of operating -40 VDC to -60 VDC at a
maximum current level 100 A.
•
Caution
: Double pole fusing.