Using the shelf manager CLI
Using the shelf manager system event log (SEL)
FortiGate-5140B Chassis Guide
01-500-156415-20151104
85
ce: LUN: 3, Sensor # 1 ("FAN IPMC")
Type: Discrete (0x6f), "OEM reserved" (0xd5)
Belongs to entity (0x1e, 96): [FRU # 0]
ce: LUN: 0, Sensor # 136 ("FW Revision ISC")
Type: Discrete (0x6f), "OEM reserved" (0xd6)
Belongs to entity (0x1e, 96): [FRU # 0]
ce: LUN: 0, Sensor # 1 ("Fan RPM")
Type: Threshold (0x01), "Fan" (0x04)
Belongs to entity (0x1e, 96): [FRU # 0]
ce: LUN: 0, Sensor # 4 ("Exhaust Temp")
Type: Threshold (0x01), "Temperature" (0x01)
Belongs to entity (0x1e, 96): [FRU # 0]
ce: LUN: 0, Sensor # 3 ("Flame Sensor")
Type: Discrete (0x6f), "OEM reserved" (0xd2)
Belongs to entity (0x1e, 96): [FRU # 0]
ce: LUN: 0, Sensor # 2 ("FAN ALARM")
Type: Discrete (0x6f), "OEM reserved" (0xd2)
Belongs to entity (0x1e, 96): [FRU # 0]
ce: LUN: 1, Sensor # 0 ("FAN Temperature")
Type: Threshold (0x01), "Temperature" (0x01)
Belongs to entity (0x1e, 96): [FRU # 0]
Sample sections of SEL Output
Shows the active shelf manager moving from M0 to M4 state (active and working):
0x0285: Event: at Jan 1 00:01:46 1970; from:(0x20,0,0);
sensor:(0xf0,0); event:0x6f(asserted): HotSwap: FRU 0 M0-
>M1, Cause=0x0
0x0286: Event: at Jan 1 00:01:51 1970; from:(0x20,0,0);
sensor:(0xf0,0); event:0x6f(asserted): HotSwap: FRU 0 M1-
>M2, Cause=0x2
0x0287: Event: at Jan 1 00:01:51 1970; from:(0x20,0,0);
sensor:(0xf0,0); event:0x6f(asserted): HotSwap: FRU 0 M2-
>M3, Cause=0x1
0x0288: Event: at Jan 1 00:01:52 1970; from:(0x20,0,0);
sensor:(0xf0,0); event:0x6f(asserted): HotSwap: FRU 0 M3-
>M4, Cause=0x0
Shows fan #2 in middle Fan Tray is spinning slower than required:
0x018D: Event: at Jan 1 00:02:15 1970; from:(0x10,0,0);
sensor:(0x04,10); event:0x1(asserted): "Upper Critical",
Threshold: 0xff, Reading: 0xff
Shows a low voltage warning on the backup battery on shelf manager 1:
0x022C: Event: at Jan 1 23:09:06 2010; from:(0x10,0,0);
sensor:(0x02,6); event:0x1(asserted): "Lower Critical",
Threshold: 0xb3, Reading: 0x99
Shows the board in ATCA slot 4 has exceeded the incoming air temperature limit: