background image

05: ECO voltage range settings

Interface

Setting

Parameter 2 & 3

:

 

Press the UP or Down key to choose the 

acceptable high and low voltage values for the ECO mode.

HLS

: High line transfer in ECO mode as set in parameter 2.

For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
(Default: +12V)

LLS

: Low line transfer in ECO mode as set in parameter 2.

For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage. 
(Default: -12V)

09: Backup time setting for outlets

00: Exit setting

3-6. Operation mode description

06: Bypass enable/disable when UPS is off

Interface

Setting

Parameter 3

:

 

Use it to activate or cancel the Bypass mode.

ENA

: Bypass enabled

DIS

: Bypass disabled

07: Bypass voltage range setting

Interface

Setting

Parameter 2 & 3

:

 

Press the UP or Down key to choose the 

acceptable high and low voltage values for Bypass operation

HLS:

 High voltage adjustment in bypass mode

For 200/208/220/230/240 VAC:

230-264:

 High voltage setting ranges from 230VAC to

264VAC as set in parameter 3. (Default: 264VAC)

LLS:

 Low voltage adjustment in bypass mode. For

200/208/220/230/240 VAC:

170-220:

 Low voltage setting ranges from 170VAC to

220VAC as set in parameter 3. (Default: 170VAC)

08: Backup time setting

Interface

Setting

Parameter 3

:

 

Sets the backup time limits for the 

programmable outlets.

0-999

: Use this setting to define the programmable outlets 

backup time in minutes, from 0-999, in order to connect 
non-critical devices on battery mode.

Interface

Setting

Parameter 3

:

 

Sets up backup interval on battery mode 

for default outlets.

0-999

: Use this setting to define the default outlets backup

interval in minutes, from 0-999, to operate on battery mode.

0

: When this parameter is set to “0”, the backup interval will 

only last 10 seconds.

999

: When this parameter is set to “999”, the backup interval 

will be disabled (Default).

Operating mode

Online mode

ECO mode

Battery mode

Bypass mode

Standby mode

Frequency
Converter mode

Description

LCD display

When the input voltage is within acceptable range, the UPS 
will supply pure and stable AC power to connected loads. 
The UPS will also charge the battery in online mode.

Energy saving mode:
When the input voltage is within the voltage regulation range,
the UPS will bypass voltage to loads for energy saving.

When input frequency is between 40 Hz and 70 Hz, 
the UPS can be set at a constant output frequency, 
50 Hz or 60 Hz. The UPS will still charge the battery when
operating in this mode.

When the input voltage exceeds the acceptable range or 
during a power failure, the UPS will start supplying power 
from the battery while the alarm will beep every 4 seconds.

When input is within acceptable voltage range but the UPS 
is overloaded, the UPS will transfer to bypass mode or it can
be manually changed to bypass mode using the front panel 
controls. The alarm will sound once every 10 seconds 
in this case.

The UPS is powered off and there is no power supplied to 
the loads, but batteries can still be charged.

Summary of Contents for FDC-1002T-A

Page 1: ...3 y e a r w a r r a n t y User Manual Uninterruptible Power Supply System FDC 1002T A 2002T A Ajustes 06_20_2017...

Page 2: ...ables for connections between mains the UPS and equipment shockproof outlet Use CE marked power cables to connect the loads to the UPS system During the installation of this equipment make sure that t...

Page 3: ...humidity is high For best performance keep the indoor temperature between 0 C and 40 C Place the UPS unit at least 20 cm away from monitors to avoid interference 2 4 UPS connections 2 4 1 UPS input c...

Page 4: ...ut frequency battery voltage output voltage and output frequency Setting mode Press and hold this button for 5 seconds to enter the UPS configuration menu while UPS is in standby or bypass mode Down k...

Page 5: ...ce Setting Parameter 3 Output voltage For 200 208 220 230 240 VAC you may choose any of the following output voltages 200 The output voltage is 200VAC 208 The output voltage is 208VAC 220 The output v...

Page 6: ...mmable outlets backup time in minutes from 0 999 in order to connect non critical devices on battery mode Interface Setting Parameter 3 Sets up backup interval on battery mode for default outlets 0 99...

Page 7: ...ocket Symptom Possible cause Solution Fault code 28 and the icon become illuminated on the LCD display and the alarm starts beeping continuously The and icons become illuminated on the LCD display and...

Page 8: ...ion 200 240VAC 160VAC 140VAC 120VAC 110VAC 5 based on load percentage 100 80 80 70 70 60 60 0 Low line transfer voltage 15V 300VAC 5 High line transfer voltage 10V 40 70Hz 0 99 at 100 load 15 at 100 l...

Reviews: