6. Technical specifications

5. Storage and maintenance

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been 
exceeded, the batteries must be replaced. In this case, please contact your dealer or service center.

Storage

Charge the UPS for at least 5 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location.
During storage, recharge the battery in accordance with the following table:

Batteries must not be discarded as regular household waste! As part of the
company’s eco-friendly approach, we encourage you to follow all applicable local
waste regulations to dispose of your used devices and batteries properly.

Storage temperature

Recharge frequency

Runtime

-25°C - 40°C

40°C - 45°C

Every 3 months

Every 2 months

1-2 hours

1-2 hours

MPN

FDC-1002T-A

FDC-2002T-A

General

Capacity

Topology

Input

Nominal voltage

Voltage range (low line transfer)

Voltage range (low line comeback)

Voltage range (high line transfer)

Voltage range (high line comeback)

Frequency

Power factor

Total harmonic distortion (THDi)

AC plug style

Output

Nominal voltage

AC voltage regulation (battery mode)

Frequency (synchronized range)

Frequency (battery mode)

Power factor

Efficiency (AC mode)

Efficiency (battery mode)

        1000VA/800W 

         2000VA/1600W

Double conversion

200-240VAC

160VAC / 140VAC / 120VAC / 110VAC ± 5%

(based on load percentage 100%-80% / 80%-70% / 70%-60% / 

60%-0%)

Low line transfer v15V

300VAC ± 5%

High line transfer voltage -10V

40-70Hz

≥0.99 at 100% load

≤15% at 100% load THDU <1.6%

IEC C14

200/208/220/230/240VAC

± 1%

47-53Hz at 50Hz system / 57-63Hz at 60Hz system

50Hz ± 0.1Hz or 60Hz ± 0.1Hz

0.8

≥88%
≥83%

≤3% THD (linear load) / ≤6% THD (non-linear load)

<1000m 

<50dB at 1 meter

Overload

Transfer time (line to battery)

Transfer time (inverter to bypass)

Crest ratio

Harmonic distortion

Waveform

Total outlets

Battery

Battery type and quantity

Recharge time

Charging current

Charging voltage

Communications

LCD display

Audible

Communication ports

Power management software

Environment

Operating temperature

Storage temperature

Relative humidity

Operating altitude

Audible noise

Physical appearance

Dimensions

Weight

Additional information

Warranty

≥0.99 at 100% load

≤15% at 100% load THDU <1.6%

≥88%
≥83%

105%-110%: 10min / 110%-130%: 1min / >130%: 3sec

0ms

4ms

3:1 (max)

≤3% THD (linear load) / ≤6% THD (non-linear load)

Pure sine wave

4 (Argentina Type I)

                12V / 9Ah (2) 

           12V / 9Ah (4)

4 hours to 90% capacity

1A ± 10% (max)

               27.4VDC ± 1% 

           54.7VDC ± 1%

Graphical LCD with blue backlight

Battery mode: Sounds every 4 seconds

Low battery: Sounds every second

Overload: Sounds every 0.5 second

Fault: Continuous sound

SNMP, RS-232, USB

ForzaTracker 

32°F-104°F  

UPS: -4°F-122°F  

20-90% non-condensing

<1000m 

Every 100m above 1000m decreases output power 1% up to 4000m

<50dB at 1 meter

                  5.7x8.7x11.1in   

5.7x8.7x15.6in  

                         22lb   

             38lb  

Three years*

* Limited to two years on batteries

Summary of Contents for FDC-1002T-A

Page 1: ...3 y e a r w a r r a n t y User Manual Uninterruptible Power Supply System FDC 1002T A 2002T A Ajustes 06_20_2017...

Page 2: ...ables for connections between mains the UPS and equipment shockproof outlet Use CE marked power cables to connect the loads to the UPS system During the installation of this equipment make sure that t...

Page 3: ...humidity is high For best performance keep the indoor temperature between 0 C and 40 C Place the UPS unit at least 20 cm away from monitors to avoid interference 2 4 UPS connections 2 4 1 UPS input c...

Page 4: ...ut frequency battery voltage output voltage and output frequency Setting mode Press and hold this button for 5 seconds to enter the UPS configuration menu while UPS is in standby or bypass mode Down k...

Page 5: ...ce Setting Parameter 3 Output voltage For 200 208 220 230 240 VAC you may choose any of the following output voltages 200 The output voltage is 200VAC 208 The output voltage is 208VAC 220 The output v...

Page 6: ...mmable outlets backup time in minutes from 0 999 in order to connect non critical devices on battery mode Interface Setting Parameter 3 Sets up backup interval on battery mode for default outlets 0 99...

Page 7: ...ocket Symptom Possible cause Solution Fault code 28 and the icon become illuminated on the LCD display and the alarm starts beeping continuously The and icons become illuminated on the LCD display and...

Page 8: ...ion 200 240VAC 160VAC 140VAC 120VAC 110VAC 5 based on load percentage 100 80 80 70 70 60 60 0 Low line transfer voltage 15V 300VAC 5 High line transfer voltage 10V 40 70Hz 0 99 at 100 load 15 at 100 l...