6. Technical specifications
5. Storage and maintenance
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been
exceeded, the batteries must be replaced. In this case, please contact your dealer or service center.
Storage
Charge the UPS for at least 5 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location.
During storage, recharge the battery in accordance with the following table:
Batteries must not be discarded as regular household waste! As part of the
company’s eco-friendly approach, we encourage you to follow all applicable local
waste regulations to dispose of your used devices and batteries properly.
Storage temperature
Recharge frequency
Runtime
-25°C - 40°C
40°C - 45°C
Every 3 months
Every 2 months
1-2 hours
1-2 hours
MPN
FDC-1002T-A
FDC-2002T-A
General
Capacity
Topology
Input
Nominal voltage
Voltage range (low line transfer)
Voltage range (low line comeback)
Voltage range (high line transfer)
Voltage range (high line comeback)
Frequency
Power factor
Total harmonic distortion (THDi)
AC plug style
Output
Nominal voltage
AC voltage regulation (battery mode)
Frequency (synchronized range)
Frequency (battery mode)
Power factor
Efficiency (AC mode)
Efficiency (battery mode)
1000VA/800W
2000VA/1600W
Double conversion
200-240VAC
160VAC / 140VAC / 120VAC / 110VAC ± 5%
(based on load percentage 100%-80% / 80%-70% / 70%-60% /
60%-0%)
Low line transfer v15V
300VAC ± 5%
High line transfer voltage -10V
40-70Hz
≥0.99 at 100% load
≤15% at 100% load THDU <1.6%
IEC C14
200/208/220/230/240VAC
± 1%
47-53Hz at 50Hz system / 57-63Hz at 60Hz system
50Hz ± 0.1Hz or 60Hz ± 0.1Hz
0.8
≥88%
≥83%
≤3% THD (linear load) / ≤6% THD (non-linear load)
<1000m
<50dB at 1 meter
Overload
Transfer time (line to battery)
Transfer time (inverter to bypass)
Crest ratio
Harmonic distortion
Waveform
Total outlets
Battery
Battery type and quantity
Recharge time
Charging current
Charging voltage
Communications
LCD display
Audible
Communication ports
Power management software
Environment
Operating temperature
Storage temperature
Relative humidity
Operating altitude
Audible noise
Physical appearance
Dimensions
Weight
Additional information
Warranty
≥0.99 at 100% load
≤15% at 100% load THDU <1.6%
≥88%
≥83%
105%-110%: 10min / 110%-130%: 1min / >130%: 3sec
0ms
4ms
3:1 (max)
≤3% THD (linear load) / ≤6% THD (non-linear load)
Pure sine wave
4 (Argentina Type I)
12V / 9Ah (2)
12V / 9Ah (4)
4 hours to 90% capacity
1A ± 10% (max)
27.4VDC ± 1%
54.7VDC ± 1%
Graphical LCD with blue backlight
Battery mode: Sounds every 4 seconds
Low battery: Sounds every second
Overload: Sounds every 0.5 second
Fault: Continuous sound
SNMP, RS-232, USB
ForzaTracker
32°F-104°F
UPS: -4°F-122°F
20-90% non-condensing
<1000m
Every 100m above 1000m decreases output power 1% up to 4000m
<50dB at 1 meter
5.7x8.7x11.1in
5.7x8.7x15.6in
22lb
38lb
Three years*
* Limited to two years on batteries