background image

General

Capacity
Topology

Input

Nominal voltage
Voltage range (low line transfer)

Voltage range (low line comeback)
Voltage range (high line transfer)
Voltage range (High Line comeback)
Frequency
Power factor
Total harmonic distortion (THDi)
AC plug style

Output

Nominal voltage

AC voltage regulation (battery mode)
Frequency (synchronized range)
Frequency (battery mode)
Power factor
Efficiency (AC mode)
Efficiency (battery mode)
Overload

Transfer time (line to battery)
Transfer time (inverter to bypass)
Crest ratio
Harmonic distortion
Waveform
Type of outlet

Battery pack (included)

Battery type and quantity
Recharge time
Charging current
Charging voltage

Communications

LCD display
Visual indicators

Audible

Communication ports
Power management software

Special features

"Cold start” option
Auto charge 

Environment

Operating temperature
Storage temperature

Relative humidity
Operating altitude

Audible noise

Physical appearance

Housing 
Color
Dimensions

Weight

Additional information

Warranty

         6000VA/6000W 

   10000VA/10000W                  6000VA/6000W 

      10000VA/10000W

Double conversion

110-300VAC

176VAC / 140VAC / 110VAC ± 3%

(based on load percentage 100%-80% / 80%-60% / 60%-0%)

Low line transfer v 10V

300VAC ± 3%

High line transfer voltage - 10V

46-54Hz at 50Hz system / 56-64Hz at 60Hz system

≥0.99 at 100% load

<4% at 100% load / <6% at 50% load

Hard wired

                                       ± 2% 

                                          ± 1%

46-54Hz at 50Hz system / 56-64Hz at 60Hz system

50Hz ± 0.1Hz or 60Hz ± 0.1Hz

1

                                      > 91% 

                                         > 94%

                                      > 90% 

                                         > 92%

AC mode: 100%-110%: 10min / 110%-130%: 1min / >130%: 1sec

Battery mode: 100%-110%: 30sec / 110%-130%: 10sec / >130%: 1sec

0ms
0ms

3:1 (max)

≤2% THD (linear load) / ≤6% THD (non-linear load) 

≤1% THD (linear load) / ≤4% THD (non-linear load)

 Pure sine wave

Terminal block

12V / 9Ah (20)

7 hours to 90% capacity

1A ± 10% (max) standard model / 4A ± 10% (max) long-run model

273VDC ± 1%

Graphical LCD with blue backlight

Status LEDs

Battery mode: Sounds every 4 seconds

Low battery: Sounds every second

Overload: Sounds every 0.5 second

Fault: Continuous sound

SNMP, RS-232, USB

ForzaTracker

Included
Included

32°F-104°F 

UPS: -5°F-140°F 

Battery: 32°F-95°F 

0 -90% non-condensing

<1000m 

Every 100m above 1000m decreases output power 1% up to 4000m

<55dB at 1 meter

ABS and metal

Black

2 years

MPN

FDC-106KMR

FDC-110KMR

FDC-206KMR

FDC-210KMR

Standard operation: 208/220/230/240VAC

With step-down isolation transformer: 

104/110/115/120VAC

Standard operation: 208/220/230/240VAC

With step-down isolation transformer: 

104/110/115/120VAC

Even when utility power is normal, there is 
no indication on the front panel and the 
alarm has gone off.
The     icon and the warning code      blink 
on the LCD display, and the alarm starts 
beeping once every second.
The     and        icons become illuminated 
on the LCD display, and alarm starts 
beeping once every second.

The     and          icons blink on the LCD 
display, and the alarm starts beeping twice 
every second.

Fault code 43 becomes illuminated along 
with the          icon on the LCD display, and 
the alarm starts beeping continuously.
Fault code 14 becomes illuminated along 
with the         icon on the LCD display, and 
the alarm starts beeping continuously.
Fault code 01, 02, 03, 04, 11, 12, 13, 14,1A, 
21, 24, 35, 36, 41, 42 or 43 become 
illuminated on the LCD display, and alarm 
starts beeping continuously.

Battery backup time is shorter than its 
nominal value.

The AC input cable is not properly 
connected.

EPO function is enabled.

The external or internal battery connection 
is incorrect.

UPS is overloaded.

UPS is overloaded. Devices connected to 
UPS are fed directly with utility power 
through Bypass 
After repetitive overloads, the UPS is 
locked in Bypass mode.
Connected devices are fed directly from 
utility power.
The UPS malfunctions due extended 
system overload.
The UPS will shut down automatically.
The UPS shuts down automatically 
because the output is short circuited.

A UPS internal fault has occurred. There 
are two

 

possible causes:

1. Power is continued to be supplied to 
the load, but is done directly from the AC 
grid via a bypass.
2. Power is no longer supplied to the load.
Batteries are not fully charged 

Defective batteries 

Check to make sure the power cord is 
firmly connected to the AC mains outlet.

Set the circuit in its closed position to 
disable the EPO function.

Check if all batteries are properly
connected.

Remove excess loads from the UPS 
output.
Remove excess loads from the UPS 
output.

Remove excess loads from the UPS 
output first. Then shut down the UPS and 
restart the unit once again.

Remove excess loads from the UPS 
output and restart the unit once again.

Check the output wiring and if the 
connected devices are short-circuited.

Contact the dealer or service center.

Charge the batteries for at least 7 hours 
and then check their capacity.
If the problem persists, consult your 
dealer.
Contact your dealer for a replacement.

Symptom

Possible cause

Solution

-25°C - 40°C
40°C - 45°C

Every 3 months
Every 2 months

1-2 hours
1-2 hours

Storage temperature

Recharge frequency

Runtime

5. Storage and maintenance 

5-1. Storage

4. Troubleshooting guide

If the UPS system does not operate correctly, use the table below to troubleshoot the problem.

Charge the UPS for at least 7 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location. During 
storage, recharge the battery in accordance with the following table:

5-2. Maintenance

The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
Even after the unit is disconnected from the mains, components inside the UPS system are still connected to the battery packs 
which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no 
hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
Servicing of batteries should be performed or supervised by personnel with knowledge of batteries and the required precau-
tions. Keep unauthorized personnel away from batteries.    
Verify that no voltage between the battery terminals and the ground is present before maintenance or repair. In this product, the 
battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the 
ground.
A battery can present a risk of electric shock and high short circuit current. The following precaution should be observed when 
working on batteries:
- Remove watches, rings or other metal objects.
- Use tools with insulated handles.
Replace batteries with the same type and number of units.
Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The batteries must be properly 
deposed according to local regulations.
Do not open or destroy batteries. Released electrolyte is highly poisonous and harmful to the skin and eyes.
Replace the fuse only with the same type and amperage in order to avoid fire hazards.
Do not disassemble the UPS system.

 

Summary of Contents for FDC-106KMR-ISO

Page 1: ...2 y e a r W a r r a n t y Ajustes 07_14_2017 User manual Uninterruptible Power Supply System FDC 106KMR ISO FDC 110KMR ISO FDC 206KMR FDC 210KMR...

Page 2: ...he UPS must be thoroughly dry before being installed Failure to do so may increase the risk of electric shock Do not install the UPS system near water or in moist environments To reduce the risk of ov...

Page 3: ...f the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS...

Page 4: ...ry ground for battery pack 22 Output breaker 23 Maintenance bypass switch 24 Output control signal slot 25 Maintenance bypass ground 26 Maintenance bypass output terminals 27 Maintenance bypass UPS ou...

Page 5: ...battery pack breaker must also be set to OFF before installing the battery pack Pay close attention to the rated battery voltage marked on the rear panel If you want to change the number of batteries...

Page 6: ...VA load max Connect X1 X3 via jumper wire Connect N N via jumper wire This will give you 120V output for 10KVA load The following connection will give you two sets of 120V outputs each output takes 5K...

Page 7: ...m the selected settings of the configuration menu Turns off the UPS Press and hold this button for 0 5 second to turn off the UPS Esc key Press this button to return to the last setting of the configu...

Page 8: ...e UPS will perform an automatic battery self test on a periodic basis The default setting for the battery self test is once per week 3 Battery self test interval can also be set through the monitoring...

Page 9: ...ixed 11 Operation in fault mode 1 When the Fault LED illuminates and the buzzer beeps continuously it means that there is a fatal error in the UPS Fault codes are available via the LCD panel Refer to...

Page 10: ...re connected correctly 4 Turn on each UPS one by one and make sure that AC mode LED or Battery mode LED display is lit in each UPS Using a multimeter measure the output voltage of each UPS to make sur...

Page 11: ...he load and complete ly shut down the UPS system 2 Enable the Bypass setting in each UPS and then power off the running UPS All UPS units in the parallel system will transfer to Bypass mode Remove all...

Page 12: ...ce Setting 03 Voltage range for bypass Parameter 3 Frequency mode Enables you to set the output frequency in either CVCF mode or no CVCF mode You may choose any of the following two options in paramet...

Page 13: ...V to 5 7V the default value is 0V Interface Setting 13 Battery voltage adjustment Parameter 2 You may choose Add or Sub to adjust the charger voltage Parameter 3 The voltage ranges from 0V to 9 9V the...

Page 14: ...ress This operation is used to check the battery status 3 9 Fault codes 3 10 Warning indicators Fault event Bus start failure Bus over Bus under Bus unbalanced Inverter soft start failure High inverte...

Page 15: ...UPS is overloaded UPS is overloaded Devices connected to UPS are fed directly with utility power through Bypass After repetitive overloads the UPS is locked in Bypass mode Connected devices are fed di...

Page 16: ...utput Nominal voltage AC voltage regulation battery mode Frequency synchronized range Frequency battery mode Power factor Efficiency AC mode Efficiency battery mode Overload Transfer time line to batt...

Page 17: ......

Reviews: