background image

Description

UPS status

Bypass mode

Battery mode

Fault mode

Warning

Overload

Other alert

Fault

All

Buzzer status

Beeps once every 2 minutes

Beeps once every 4 seconds

Beeps continuously

Beeps twice every second

Beeps once every second

Beeps continuously

Yes

Yes

Yes

Muted

2) Press and hold the 

ON

 button for 0.5 second to power on the UPS. The buzzer will beep once.

3) After a few seconds, the UPS will enter into the AC mode. In case of abnormal utility power, the UPS will transfer to battery        
    mode operation to provide uninterrupted power to the outlets.

Note:

 In battery mode, the UPS will shut down automatically when the remaining charge is low. Once the utility power is 

restored, the UPS will restart automatically in AC mode.

2. Turn on the UPS without utility power (Battery mode)

1) Make sure that the battery pack breaker is in its 

ON

 position.

2) Press and hold the 

ON

 button for 0.5 second to power on the UPS. The buzzer will beep once.

3) After a few seconds, the UPS will be turned on and begin operating on “off-grid” or Battery mode.

3. Connecting devices to the UPS

After the UPS is turned on, you can connect devices to the unit.

1) Turn on the UPS first and then start powering one load at a time only after all of them have been plugged into the unit. The total      
    load level will be displayed on the LCD panel.
2) Should you need to connect inductive loads, such as a monitor or a laser printer to the UPS, the start-up power should be used        
    for calculating the capacity of the UPS, as energy consumption increases during initial power on.
3) If the UPS is overloaded, the  buzzer will beep twice every second.
4) In the event of an overload, all unnecessary loads must be removed one by one, to lower the total loads connected to the UPS to  
    less than 80% of its nominal power capacity to prevent the overload condition.
5) If the overload time exceeds the time specified in AC mode, the UPS will automatically transfer to Bypass mode. After the  

     

    overload is removed, the UPS will return to AC mode. If the overload time exceeds the time specified in Battery mode, the UPS        
    will transfer to fault status. At this time, if the bypass is enabled, the UPS will supply power to the loads using the bypass mode.      
    If the bypass function is disabled or the input power is not within the bypass acceptable range, the output power will be cut off       
    immediately.

4. Charging the batteries

1) Once the UPS is connected to utility power, the unit will charge the batteries automatically, except when the UPS is running in       
    Battery mode or  while the battery self-test is in progress.
2) It is recommended to charge the batteries at least 10 hours before use to ensure proper backup time.  
3) Verify that  battery number setting on  the control board is consistent with  the  actual quantity of  units being connected.

5. Battery mode operation

1) When the UPS is in Battery mode, the buzzer will beep according to the battery capacity.

a. If the battery capacity is over 25%, the buzzer will beep once every 4 seconds.
b. If the battery voltage drops to the alarm triggering level, the buzzer will beep once every second to indicate that the battery has 
reached its lowest capacity, and that the UPS will soon shut down automatically. Shutting down non-critical loads at this point 
will disable the alarm and prolong the backup time. If the programmable timer function is enabled, the UPS will shut off program-
mable output terminals automatically.

Note:

 Should there be no more loads to turn off, you will need to shut down all existing connected equipment as soon as 

possible to protect it or save the data. There is the risk of data loss or load failure if battery runtime is exceeded.

2) To silence the buzzer sound in Battery mode, press the Mute button.
3) The backup time varies depending upon the capacity of the external batteries being used.
4) When the backup time is set at 16.5 hours (LCD panel default value), the UPS will shut down automatically to protect the battery      
    after the discharging period expires. This battery discharge protection can be enabled or disabled using the LCD panel control.

6. Testing the batteries

1) To check the battery status when the UPS is running in AC mode/CVCF mode/ECO mode, press the 

Test

 button to initiate the        

    self-diagnostic tool.
2) To maintain the system reliability, the UPS will perform an automatic battery self-test on a periodic basis. The default setting for        
    the battery self -test is once per week.
3) Battery self-test interval can also be set through the monitoring software.
4) When the UPS is in battery self-test mode, the LCD Display and buzzer indication will be the same as in battery mode, with the       
    exception that the battery LED will appear blinking in this case.

7. Turn off the UPS with utility power in AC mode

1) Turn off the inverter of the UPS by pressing the 

OFF

 button for at least 0.5 second. The buzzer will beep once and the UPS will      

    go into Bypass mode.

Note 1:

 If the UPS has been set to enable the bypass output, it will bypass voltage from utility power to the output terminal even 

though the UPS (inverter) has been turned off.

Note 2:

 After turning off the UPS, please beware that the UPS is operating in Bypass mode and there is a risk of power loss for 

connected devices.

2) In Bypass mode, output voltage of the UPS is still present. In order to shut off the output voltage, switch off the input breaker to    
    the UPS. A few seconds later, there will be no display shown on the LCD panel while the UPS is now completely turned off.

8. Turn off the UPS without utility power supply in Battery mode

1) Turn off the UPS by pressing the OFF button for at least 0.5 second. The buzzer will beep once.
2) The UPS will cut off power to the output, in which case there will be no indication showing on the display panel.

9. Muting the buzzer

1) To silence the buzzer, press the Mute button for at least 0.5 second. If you press it again, the buzzer will be enabled.
2) Some warning alarms cannot be muted unless the error that triggered them is fixed.

10. Operation in warning status

1) When the Fault LED flashes and the buzzer beeps  once  every  second, it means that the UPS is experiencing operation issues.     
    Fault codes are available via the LCD panel. Refer to the troubleshooting table for additional details.
2) Some warning alarms cannot be muted unless the error that triggered them is fixed.

11. Operation in fault mode

1) When the Fault LED illuminates and the buzzer beeps continuously, it means that there is a fatal error in the UPS. Fault codes are  
    available via the LCD panel. Refer to the Troubleshooting table for additional details.
2) Check the loads, wiring, ventilation, utility, battery and so on when a fault occurs. Do not try to turn on the UPS again before  

     

    solving the problems. If the issues persist, contact the dealer or service personnel immediately.
3) In case of emergency, disconnect the UPS from the utility, external battery, and output immediately to avoid danger.

12. Changing battery numbers

1) This operation should only be performed by trained and qualified technicians.
2) Turn off the UPS. If the load cannot be shut down, remove the cover from the maintenance bypass switch on the rear panel of       
    the unit, and slide the maintenance switch to the BPS position.
3) Switch off the input breaker and battery breaker.
4) Remove the UPS cabinet cover. Disconnect the battery wire and modify the jumper on the control board to set the battery  

     

    numbers, as shown on the table below.  

5) Modify the battery pack to match the setting number in control panel.

6) Then, modify charger voltage according to the table below to match the setting number on the control board. There are 5     

    

    jumpers on the charger board. Please refer to the below table to modify charger voltage.

7) After executing the previous steps, replace the UPS cover. Switch on the battery breaker  followed by the input breaker. The UPS 
will enter into the Bypass mode. If the UPS is in maintenance Bypass mode, turn the maintenance switch to the 

UPS

 position 

before turning on the system.

13. Changing charging current

1) This operation should only be performed by trained and qualified technicians.
2) Turn off the UPS. If the load could not be cut off, you should remove the cover of maintenance bypass switch on the rear panel       
    and turn the maintenance switch to the 

BPS

 position first. 

3) Switch off the input breaker and then do the same with the battery breaker.
4) Remove the cabinet cover and disconnect battery wire. Then modify the jumpers on the charger board to set the charging  

     

    current (refer to table below). Be careful that the maximum setting should not exceed the charging current acceptable for the  

    

    battery.

3.5 Parallel system operation

1. Parallel system installation 

If the UPS is only available for single operation, you may skip this section to the next.

1) Install and wire the UPS units according to section 3.5.2 in this manual.
2) Connect the output wires of each UPS to an output breaker or maintenance bypass switch with an output breaker
    (sold separately).
3) Connect all output breakers to a maintenance bypass switch with breaker.
4) Each UPS must be connected to its own power bank. In the event a single power bank is used for all the UPS units, it will cause   
    permanent damage to the equipment.
5) Remove the cover of the parallel share current cable port on the UPS. Connect each UPS one by one with the parallel cable and      
    share current cable, and then screw the cover back again.
6) Refer to the following wiring diagram. 

Input and battery voltage information

Battery information

Indicates the battery is charged at 0-25%, 26-50%, 51-75%, and 

76-100% of its capacity.

Indicates the input voltage or frequency, or battery voltage.

VAC: input voltage  VDC: battery voltage Hz: input frequency

Indicates the battery is not connected.

Low battery and low voltage indicator.

Indicates that the UPS is connected to the mains.

Indicates the battery is in working status.

Indicates the bypass circuit is in working status.

Indicates the ECO mode is enabled.

Indicates the inverter circuit is working.

Indicates the output connector is working properly.

Mode operation information

Input and battery voltage information

Battery information

Indicates the load level at 0-25%, 26-50%, 51-75%, and 76-100%

Indicates the battery is charged at 0-25%, 26-50%, 51-75%, and 

76-100% of its capacity.

Indicates the input voltage or frequency, or battery voltage.

VAC: input voltage  VDC: battery voltage Hz: input frequency

Overload indication.
Indicates the load or the output is short-circuited.

Indicates the battery is not connected.

Low battery and low voltage indicator.

Indicates that the UPS is connected to the mains.

Indicates the battery is in working status.

Indicates the bypass circuit is in working status.

Indicates the ECO mode is enabled.

Indicates the inverter circuit is working.

Indicates the output connector is working properly.

3-3. Audible alarm

3-4. Single UPS operation

1. Turn on the UPS with utility power (On grid/ AC mode)

1) In order for this equipment to operate properly, first you need to make sure that the connection between the UPS and the   

   

    power pack is correct. Then set the battery pack breaker to its 

ON

 position. Next, set the UPS breaker to its 

ON

 position. At          

    this point, the fan will start running while the UPS supplies power to the loads via the bypass. This means that the UPS has       
    begun operating in Bypass mode.  

Caution: 

To maintain the system reliability, make sure to follow the correct sequence when powering on the equipment.   

Note:

 When the UPS is in Bypass mode, the output voltage will directly power the loads from utility after you have switched on 

the input breaker. In  Bypass Mode, the load is not protected by the UPS. To protect your load devices, you should turn on the 
UPS as explained below.

Summary of Contents for FDC-106KMR-ISO

Page 1: ...2 y e a r W a r r a n t y Ajustes 07_14_2017 User manual Uninterruptible Power Supply System FDC 106KMR ISO FDC 110KMR ISO FDC 206KMR FDC 210KMR...

Page 2: ...he UPS must be thoroughly dry before being installed Failure to do so may increase the risk of electric shock Do not install the UPS system near water or in moist environments To reduce the risk of ov...

Page 3: ...f the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS...

Page 4: ...ry ground for battery pack 22 Output breaker 23 Maintenance bypass switch 24 Output control signal slot 25 Maintenance bypass ground 26 Maintenance bypass output terminals 27 Maintenance bypass UPS ou...

Page 5: ...battery pack breaker must also be set to OFF before installing the battery pack Pay close attention to the rated battery voltage marked on the rear panel If you want to change the number of batteries...

Page 6: ...VA load max Connect X1 X3 via jumper wire Connect N N via jumper wire This will give you 120V output for 10KVA load The following connection will give you two sets of 120V outputs each output takes 5K...

Page 7: ...m the selected settings of the configuration menu Turns off the UPS Press and hold this button for 0 5 second to turn off the UPS Esc key Press this button to return to the last setting of the configu...

Page 8: ...e UPS will perform an automatic battery self test on a periodic basis The default setting for the battery self test is once per week 3 Battery self test interval can also be set through the monitoring...

Page 9: ...ixed 11 Operation in fault mode 1 When the Fault LED illuminates and the buzzer beeps continuously it means that there is a fatal error in the UPS Fault codes are available via the LCD panel Refer to...

Page 10: ...re connected correctly 4 Turn on each UPS one by one and make sure that AC mode LED or Battery mode LED display is lit in each UPS Using a multimeter measure the output voltage of each UPS to make sur...

Page 11: ...he load and complete ly shut down the UPS system 2 Enable the Bypass setting in each UPS and then power off the running UPS All UPS units in the parallel system will transfer to Bypass mode Remove all...

Page 12: ...ce Setting 03 Voltage range for bypass Parameter 3 Frequency mode Enables you to set the output frequency in either CVCF mode or no CVCF mode You may choose any of the following two options in paramet...

Page 13: ...V to 5 7V the default value is 0V Interface Setting 13 Battery voltage adjustment Parameter 2 You may choose Add or Sub to adjust the charger voltage Parameter 3 The voltage ranges from 0V to 9 9V the...

Page 14: ...ress This operation is used to check the battery status 3 9 Fault codes 3 10 Warning indicators Fault event Bus start failure Bus over Bus under Bus unbalanced Inverter soft start failure High inverte...

Page 15: ...UPS is overloaded UPS is overloaded Devices connected to UPS are fed directly with utility power through Bypass After repetitive overloads the UPS is locked in Bypass mode Connected devices are fed di...

Page 16: ...utput Nominal voltage AC voltage regulation battery mode Frequency synchronized range Frequency battery mode Power factor Efficiency AC mode Efficiency battery mode Overload Transfer time line to batt...

Page 17: ......

Reviews: