4. Troubleshooting guide

If the UPS system does not operate correctly, use the table below to troubleshoot the problem

5. Storage and maintenance

Maintenance 

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been 

exceeded, the batteries must be replaced. In this case, please contact your dealer or service center.

Storage

Charge the UPS for at least 5 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location. During storage, 

recharge the battery in accordance with the following table

Symptom

Possible cause

Solution

Even though the mains supply is 

normal, there are no status indica-

tors or alarms

Check to make sure the power cord is 

firmly connected to a AC wall socket

The AC input cable is not properly 

connected

The     icon and the warning code   

become illuminated on the LCD 

display, and the alarm starts 

beeping once every 2 seconds

Plug the power cord to a wall socket

The AC input is connected to the 

UPS outlet

Set the circuit in its closed position to 

disable the EPO function

EPO function is enabled

Rotate mains power socket by 180° and 

then connect to UPS system

Line and neutral conductors of UPS 

input are reversed

Check if all batteries are properly 

connected

The external or internal battery 

connection is incorrect

Contact your dealer or service center

Battery voltage is too high or the 

charger fails

Please contact the dealer or service 

center

Battery voltage is too low or the 

charger fails

Remove excess loads from UPS output

UPS is overloaded

Remove excess loads from the UPS 

output

Input current is above the accept-

able limits 

The     icon and the      warning code 

become illuminated on the LCD 

display, and the alarm starts beeping 

once every 2 seconds

The      and       icons become 

illuminated on the LCD display and 

the alarm starts beeping once every 

2 seconds
Fault code 27 and the         icon 

become illuminated on the LCD 

display, and the alarm starts 

beeping continuously
Fault code 28 and the         icon 

become illuminated on the LCD 

display and the alarm starts beep-

ing continuously

The     ,                 icons and the   

become illuminated on the LCD 

display, and the alarm starts 

beeping every second

Fault code 49 becomes illuminated 

and the alarm starts beeping 

continuously
Fault code 43 becomes illuminated 

along with the                icon on the 

LCD display, and the alarm starts 

beeping continuously

Battery backup time is shorter than 

its nominal value

Charge the batteries for at least 5 hours 

and then check their capacity. If the 

problem persists, consult your dealer

Batteries are not fully charged

Fault code 2A appears on the LCD 

display while the alarm beeps 

continuously

Check to make sure that the wiring of 

the external battery pack connected is 

not shorted 

Short circuit detected on the char-

ger output  

Fault code 45 appears on the LCD 

display while the alarm beeps 

continuously

Please contact the dealer or service 

center

There is no output voltage from the 

charger and the battery voltage is 

below 10V/PC

Contact your dealer for a replacement

Defective batteries

Remove excess loads from the UPS 

output

UPS is overloaded. Devices 

connected to the UPS are fed 

directly from utility power via the 

Bypass

Remove excess loads from the UPS 

output first. Shut down the UPS com-

pletely before restarting the unit once 

again

After repetitive overloads, the UPS 

is locked in Bypass mode. Connect-

ed devices are fed directly from 

utility power

Remove excess loads from the UPS 

output and restart the unit once again

The UPS shuts down automatically 

upon detecting the overload condi-

tion in the output

Fault code 14 becomes illuminated 

and the alarm starts beeping 

continuously

Check the output wiring and if connect-

ed devices are short-circuited

Fault codes 01, 02, 03, 11, 12, 13 

and 41 become illuminated on the 

LCD display, and the alarm starts 

beeping continuously

Please contact the dealer or service 

center

The UPS shuts down automatically 

upon detecting the overload condi-

tion in the output
A UPS internal fault has occurred. 

There are two possible causes:

1. Power is continued to be supplied 

to the load, but is done directly from 

the AC grid via a bypass

2. Power is no longer supplied to 

the load

Batteries must not be discarded as regular household waste! As part of the company’s 
eco-friendly approach, we encourage you to follow all applicable local waste regulations 
to dispose of your used devices and batteries properly.

-25°C - 40°C
-40°C - 45°C

Every 3 months
Every 2 months

1-2 hours
1-2 hours

Storage temperature

Recharge frequency

Runtime

Summary of Contents for FDC-2012R-I

Page 1: ...2 y e a r w a r r a n t y Ajustes 05_19_2017 User Manual Uninterruptible Power Supply System FDC 2012R I FDC 3012R I ...

Page 2: ...ertified electrical cables for input and output connections During the installation of this equipment make sure that the sum of the leakage currents of the UPS and the connected loads shall not exceed 3 5 mA CAUTION The unit is heavy Lifting the unit requires a minimum of two people 1 4 Important safety instructions Do not disconnect the mains cable on the UPS system or the building wiring outlet ...

Page 3: ...e of damage be found or if some parts are missing do not turn the UPS on you must immediately notify the carrier or dealer where you purchased the unit 2 2 UPS diagram Front view Rear view FDC 2012R I FDC 3012R I 1 Programmable outlets for non critical loads 2 Dedicated outlets for critical loads 3 AC input 4 Modem phone network surge protection 5 USB communication port 6 RS 232 communication port...

Page 4: ...tep 3 Verify that the UPS is stable and firmly attached to the base Intelligent slot RS 232 port USB port To allow for unattended UPS shutdown start up and status monitoring connect one end of the communication cable to the USB RS 232 port and the other end to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown start up and monitor its status thro...

Page 5: ...nter button Select button ON Mute Select button Turn on the UPS Press and hold the ON Mute button for at least 2 seconds to turn on the UPS Mute the alarm When the UPS is on battery mode press and hold this button for at least 3 seconds to disable or enable the alarm system This command would not apply when warnings or errors occur Up key Press this button to display previous selection in the UPS ...

Page 6: ...oltage output voltage and output frequency V voltage Hz frequency Indicates that the programmable management outlets are working Indicates that the UPS is connected to utility power Indicates that the battery is working Indicates the charging status Indicates the UPS is working in bypass mode Indicates the UPS is working in ECO mode Indicates the UPS is working in converter mode Battery level indi...

Page 7: ... 50 The output frequency is set to 50Hz CF 60 The output frequency is set to 60Hz Parameter 2 Activates or cancels the ECO mode Two options are available ENA ECO mode enable DIS ECO mode disable Default Parameter 2 Use this menu to set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key HLS High loss voltage in ECO mode For 200 208 220 230 240 VAC mo...

Page 8: ...feature ENA Programmable outlets enabled DIS Programmable outlets disabled Default 10 Backup time setting for programmable outlets Interface Setting Parameter 2 Sets the backup time limits for the programmable outlets 0 999 Use this setting to define the programmable outlets backup time in minutes from 0 999 in order to connect non critical devices on battery mode Default 999 12 Battery total Ah s...

Page 9: ...he connection of an external output isolation transformer ENA If selected the UPS will be allowed to connect to an external output isolation transformer DIS If selected the UPS will be denied to connect to external output isolation transformer Default 18 Runtime setting display Interface Setting Parameter 2 Use this setting to configure the runtime on the display EAT If EAT is selected it will sho...

Page 10: ...in acceptable range the UPS will supply pure and stable AC power to connected loads The UPS will also charge the battery while in online mode ECO mode Efficiency Corrective Optimizer Frequency converter mode Energy saving mode When the input voltage is within the voltage regulation range the UPS will bypass voltage to loads for energy saving The UPS will also charge the battery while in ECO mode W...

Page 11: ... beeping every second Fault code 49 becomes illuminated and the alarm starts beeping continuously Fault code 43 becomes illuminated along with the icon on the LCD display and the alarm starts beeping continuously Battery backup time is shorter than its nominal value Charge the batteries for at least 5 hours and then check their capacity If the problem persists consult your dealer Batteries are not...

Page 12: ...gement software Environment Operating temperature Storage temperature Relative humidity Operating altitude Audible noise Physical appearance Dimensions Weight Cord length Additional information Warranty 2000VA 2000W 3000VA 3000W Double conversion 200 240VAC 175VAC 155VAC 135VAC 125VAC 3 based on load percentage 100 80 80 70 70 60 60 0 Low line transfer voltage 10V 300VAC 3 High line transfer volta...

Page 13: ......

Reviews: