01: Output voltage settings
02: Frequency converter enable/disable
03: Output frequency settings
04: ECO enable/disable
05: ECO voltage range setting
06: Bypass enable/disable
07: Bypass voltage range setting
Interface
Setting
Interface
Setting
Interface
Setting
Interface
Setting
Interface
Setting
Interface
Setting
Interface
Setting
Parameter 2: Output voltage
For 200/208/220/230/240 VAC, you may choose any of the
following output voltages
200:
The output voltage is 200VAC
208:
The output voltage is 208VAC
220:
The output voltage is 220VAC
230:
The output voltage is 230VAC (Default)
240:
The output voltage is 240VAC
Parameter 2:
Activates or cancels the converter mode. You
may choose one of the options below:
CF ENA:
Enable converter mode
CF DIS:
Disable converter mode (Default)
Parameter 2:
Use this menu to define the initial frequency
on battery mode:
BAT 50:
The output frequency is set to 50Hz
BAT 60:
The output frequency is set to 60Hz
If the converter mode is enabled, the following options will
be available:
CF 50:
The output frequency is set to 50Hz
CF 60:
The output frequency is set to 60Hz
Parameter 2:
Activates or cancels the ECO mode. Two
options are available:
ENA:
ECO mode enable
DIS:
ECO mode disable (Default)
Parameter 2:
Use this menu to set the acceptable high voltage
point and low voltage point for ECO mode by pressing Down
key or Up key.
HLS:
High loss voltage in ECO mode.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
(Default: +12V)
LLS:
Low loss voltage in ECO mode.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage. (Default:
-12V)
Parameter 2:
Use it to activate or cancel the bypass feature
when the UPS is off.
ENA:
Bypass enabled
DIS:
Bypass disabled
Parameter 2:
Press the
UP
or
Down
key to choose the
acceptable high and low voltage values for Bypass operation
HLS:
High voltage adjustment in bypass mode
For 200/208/220/230/240 VAC:
230-264:
High voltage setting ranges from 230VAC to 264VAC
as set in parameter 3. (Default: 264VAC)
LLS:
Low voltage adjustment in bypass mode. For
200/208/220/230/240 VAC:
170-220:
Low voltage setting ranges from 170VAC to 220VAC
as set in parameter 3. (Default: 170VAC)