ISSUE DATE 10-09-03 REV. DATE 12/17 REV. LEVEL: 17 ECO 1-7383 OIPM P/N 8329
MAINTENANCE
Pre-Season Maintenance and Annual Inspection
To ensure your safety and for years of trouble-free operation of the heating system, annual service
and inspections must be done by a qualified contractor.
To obtain maximum performance from your heater(s) each year, we recommend the following be
performed at the start of the heating season:
1.Clean reflector surface with a damp cloth.
2. Clean quartz lamp with alcohol moistened soft cloth.
3. Make sure heater is secure on all hanging points.
4.
Maintain the Clearance to Combustibles.
Immediately remove objects in violation of the
clearance to combustibles.
If additional service to the heater is required, contact the factory or your local representative
.
TROUBLESHOOTING
SYMPTOM
POSSIBLE CAUSE(S)
CORRECTIVE ACTION
Element does not energize
1. Defective element.
2. Improper connection.
3. Pigtail loose from socket connection.
1. Replace element.
2. Check connection to power source.
3. Rewind or re-insert pigtail into socket.
Not enough heat.
1. Heater too small for application.
2. Heater mounted too high or too far.
1. Add more heaters.
2. Decrease mounting height or distance.
Too much heat.
1. Heater too large for application.
2. Heater mounted too low or too close.
1. Replace with smaller heater.
2. Increase mounting height or distance.
13
WARNING: WHEN ADJUSTING MOUNTING HEIGHT FOR MORE OR LESS HEAT, STAY WITHIN
RECOMMENDED MOUNTING HEIGHTS ON PAGE 7.