Goodrive20 Series VFD
Function parameter list
-48-
Function
code
Name
Description
Default Modify
two groups of parameters. See the following
figure.
Output frequency f
P03.00, P03.01
P03.02
P03.05
P03.03, P03.04
PI parameter
PI parameters have a close relationship with
the inertia of the system. Adjust PI
parameters depending on different loads to
meet various demands.
Setting range of
P03.00
and
P03.03
:
0
–200.0
Setting range of
P03.01
and
P03.04
:
0.000
–10.000s
Setting range of
P03.02
: 0.00Hz
–
P03.05
Setting range of
P03.05
:
P03.02
–
P00.03
(max. output frequency)
P03.06
Speed loop
output filter
0
–8 (corresponding to 0–2
8
/10ms)
0
○
P03.07
Electromoti
on slip
compensati
on
coefficient
of vector
control
Slip compensation coefficient is used to
adjust the slip frequency of the vector control
and improve the speed control accuracy of
the system. Adjusting the parameter properly
can control the speed steady-state error.
Setting range: 50%
–200%
100%
○
P03.08
Brake slip
compensati
on
coefficient
of vector
control
100%
○
P03.09
Current
loop
percentage
coefficient
P
Note
:
The two function codes impact the
dynamic response speed and control
accuracy of the system. Generally, you do
not need to modify the two function
1000
○
Summary of Contents for GD20-004G-2
Page 1: ......