Goodrive20 Series VFD
Function parameter list
-79-
Function
code
Name
Description
Default
Modify
interval from when a fault occurred to
when automatic fault reset takes effect.
Setting range of
P08.28
: 0
–10
Setting range of
P08.29
: 0.1
–100.0s
P08.30
Frequency
decrease ratio
in drop control
The output frequency of the VFD changes
as the load changes. The function code is
mainly used to balance the power when
several motors drive a same load.
Setting range: -50.00Hz
–+50.00Hz
0.00Hz
○
P08.32
FDT1
electrical level
detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical
level, the multi-function digital output
terminals continuously outputs the signal
of "Frequency level detect FDT". The
signal is invalid only when the output
frequency decreases to a value lower than
the frequency corresponding to (FDT
electrical level
—FDT lagging detection
value) The waveform diagram is as
follows:
Output frequency f
FDT level
Y, RO1, RO2
FDT lag
Time t
Time t
Setting range of
P08.32
: 0.00Hz
–
P00.03
(max output frequency)
Setting range of
P08.33
and
P08.35
:
0.0
–100.0%
Setting range of
P08.34
: 0.00Hz
–
P00.03
(max output frequency)
50.00Hz
○
P08.33
FDT1 lagging
detection
value
5.0%
○
P08.34
FDT2
electrical level
detection
value
50.00Hz
○
P08.35
FDT2 lagging
detection
value
5.0%
○
P08.36
Detection
value for
frequency
being reached
When the output frequency is within the
detection range, the multi-function digital
output terminal outputs the signal of
"Frequency reached".
0.00Hz
○