Integrated interfaces
23
An RS485 interface is available at connection terminal
KX1
(COM2).
The configuration of the interface is described in the
"FP-SPS-TiXML-Manual".
6.3
M-Bus Interface
A fully-fledged M-Bus master is available at connection ter-
minal
KM1
.
The configuration of the interface is described in the
"FP-SPS-TiXML- Manual".
6.4
S0 Pulse inputs
(Model series W550)
Technical data and programming of the S0 pulse inputs are de-
scribed in the chapter 7.2.
Key figures at a glance
– W600 models:
M-Bus master for 50 slaves (optional: 100 Slaves)
– W500 models:
M-Bus master for 25 slaves
– Open circuit voltage: 36 V
– Ri = approx. 20 Ω
– Short-circuit proof, galvanic isolation: 1,500 V
– W600 models: max. bus length: 50 m, grid dimension
3.81 mm, cross-section max. 1.5 mm²
– W500 models: max. bus length: 50 m, grid dimension
5.08 mm, cross-section max. 1.5 mm²
– Name of connection terminal:
KM1
Key figures at a glance
– 3x pulse inputs according to IEC 62053-31 for passive S0
devices (contacts)
– Module address:
C03E
– Name of connection terminal:
S0 interface