28
“Voltage measurement” operating mode
The “Voltage measurement” operating mode can be selected
separately for each of the four inputs. In this operating mode,
voltages of 0 to 10 V can be measured against earth (factory
setting).
Activation of the
voltage measure-
ment
Set both switches of a channel to "P", e.g. for channel AI_1 the
switches SA1 and SA2.
Configure the InputMode for the according input to "U" in
the peripheral configuration or leave out the InputMode.
Assignment of the
screw terminals
The left screw terminal of an input (AI_1.1, AI_2.1, AI_3.1, AI_4.1)
is the earth connection.
The right screw terminal (AI_1.2, AI_2.2, AI_3.2, AI_4.2) is the
voltage input.
Voltage
Earth