30
“Current measurement active” operating mode
The "Current measurement active" operating mode for current
loop sensors (e.g. for pressure, temperature) can be selected
separately for each of the four inputs. A current-limited supply
voltage of approx. 24 V is provided for each sensor.
Activation of ac-
tive current meas-
urement
Set both switches of an input to "A", e.g. for input AI_1 the
switches SA1 and SA2.
Configure the peripheral configuration:
InputMode for the respective input to "I".
Assignment of the
screw terminals
The left screw terminal of an input (AI_1.1, AI_2.1, AI_3.1, AI_4.1)
is the negative connection.
The right screw terminal (AI_1.2, AI_2.2, AI_3.2, AI_4.2) is the
positive connection.