Configuration manual FP S-ENGuard
54
[<SetConfig _="PROCCFG" ver="y">
<Periphery>
<Module Name="S1-AE3" Address="C6
94
">
<!-- Channel 1 = Analogue Input (1) -->
<Numerator0_="
10000
"/>
<Denominator0_="
2047
"/>
<!-- Channel 2 = Analogue Input (2) -->
<Numerator1_="
10000
"/>
<Denominator1_="
2047
"/>
<!-- Channel 3 = Analogue Input (3) -->
<Numerator2_="
10000
"/>
<Denominator2_="
2047
"/>
<!-- These values apply to all channels -->
<Tolerance_="1"/>
<Rate_="1000"/>
</Module>
</Periphery>
</SetConfig>]
When setting 0 to 20 mA for the analogue inputs, the periph-
eral database must be adapted (e.g. Numerator
X
_="
2000
", De-
nominator
X
_="
2047
";
X
= channel number 0 to 2). In this case
the current value 0 to 20 mA is mapped to the values 0 to 2000.
Summary of Contents for 50.0070.0001.00
Page 1: ...Configuration manual FP S ENGuard ...
Page 92: ...Configuration manual FP S ENGuard 92 ...
Page 96: ...Notes 96 ...
Page 97: ...Notes 97 ...
Page 98: ...51 0070 9031 00 Rev 00 2020 08 xxx helbig berlin ...