Expansion modules
61
If a channel is synchronised by channel 1, then the synchronised
channel counts relatively. The displayed count value is always
the number of pulses during the last measuring cycle!
Example:
SyncPeriod
(optional):
Time between two synchronous pulses in seconds.
Default is 900 = 15 minutes.
Is only used for the channels for which no synchronous input is
configured.
Scaling for each
channel X (X=1-3)
Numerator/Denominator
NumeratorX
(optional)
Multiplier for the counted pulses.
DenominatorX
(optional)
Number of pulses per energy unit. Must be >0.
StartValueX
(optional; X=1-3)
Specifies the start value for each channel.
abs
Absolute count, synchronised by
SyncPeriod
.
During synchronisation the counted value is copied into a
read-only variable and the internal channel counter is not
reset.
rel
Relative count, synchronised by
SyncPeriod
.
During synchronisation the counted value is copied into a
read-only variable and the internal channel counter is
reset to 0.
sync1, off
Channel 2 is synchronised by channel 1. Channel 3 is not used.
sync1, rel
Channel 2 is synchronised by channel 1. Channel 3 counts in relative
mode (synchronised by
SyncPeriod
).
sync2
Channel 2 and channel 3 are synchronised by channel 1.
rel, abs, off
Channel 1 counts relatively. Channel 2 absolutely. Both channels are
synchronised by
SyncPeriod
. Channel 3 is not used.