Configuration manual FP S-ENGuard
78
7.6
S1-AA2
(2 analogue outputs)
The analogue outputs can be switched between 0 to 10 V and
0 to 20 mA via jumpers. The factory setting is 0 to 10 V.
The D/A converters of the analogue outputs use raw values be-
tween 0 and 4035 (corresponds to 0 to 10 V).
Key figures at a glance
– 2x analogue outputs; resolution 12bit
– Voltage output: 0 to 10 V, Ri=100 kΩ
– Current output: 0 to 20 mA, Ri=120 Ω
– Default address for automatic detection:
0x18/0x1A
Not allowed!