Expansion modules
85
In the "voltage = U" and "current = I passive" (factory setting)
operating mode the lower jumpers per channel must be set to
"A" (2 jumpers per channel). In "current = I passive" mode the
module behaves like a S1-AE3 in "I” mode.
In the "voltage = U" and "current = I passive" operating mode
the lower jumpers per channel must be set to "A" (2 jumpers per
channel).
In active mode (for current loop sensors), a current limited
voltage of approx. 24 V is provided to supply the sensor. This
changes the assignment of the screw terminals.
The A/D converters of the analogue inputs provide raw values
between 0 and
2029
. This corresponds to voltage values from
0 to 10 V and current values from 0 to 20 mA.
To scale the values to 0 to
10000
, the PROCCFG database must
be configured. The module is jumpered to address
94
, plugged
into socket 5, therefore bus number
6
.
[<SetConfig _="PROCCFG" ver="y">
<Periphery>
<Module Name="S1-AE3" Address="C
6
94
">
<!-- Channel 1 = Analogue Input (1) "Ch1.x"
-->
<Numerator0_="
10000
"/>
<Denominator0_="
2029
"/>
<!-- Channel 2 = Analogue Input (2) "Ch2.x"
-->
<Numerator1_="
10000
"/>
<Denominator1_="
2029
"/>
<!-- Channel 3 = Analogue Input (3) "Ch3.x
-->
<Numerator2_="
10000
"/>
<Denominator2_="
2029
"/>
<!-- Values apply to all channels -->
<Tolerance_="1"/>
<Rate_="1000"/>
</Module>
</Periphery>
</SetConfig>]