Expansion modules
89
7.8.1 Restrictions for the operation of passive sensors
Due to the limitation of the power supply units used, the fol-
lowing restrictions apply to the operation of passive sensors on
S1-AE203 and S1-AE3.P depending on the model.
FP S-ENGuard
Model series
W640, W667
If the 24V terminal (KP24) is loaded
and
the integrated ana-
logue outputs are not operated as current outputs, max. 1
module S1-AE203/S1-AE3.P can be used.
If the 24V terminal (KP24) is not loaded
and
the integrated an-
alogue outputs are not operated as current outputs, max. 2
modules S1-AE203/S1-AE3.P can be used.
FP S-ENGuard
Model series
W550
The S1-AE203/S1-AE3.P modules can only be operated on a de-
vice of the W550 model series with active sensors.