7.9
S1-D30G
(3 digital inputs, galvanically isolated)
The S1-D30G expansion module offers 3 digital inputs which
are electrically isolated from each other. Each of the three chan-
nels has a status LED which lights up red at high level.
Configuration of the modules is not necessary.
Key figures at a glance
– 3x digital inputs, galvanically isolated
– Low: 0 to +9.2 V, High: +10.4 V to +60 V
– Maximum input voltage: -60 V to +60 V
– Input current: 2.2 to 3.1 mA
– Creepage and clearance distance between individual
inputs: 0.8 mm
– Creepage and clearance distance between external input
and internal circuit: 2.2 mm
– Default module address:
0x40
(all 3 jumpers in position 0)
Module Address