Inline 3000 Series Cabinets
Ventilation
REFRIGERATED CABINETS
-
MECHANICAL DRAWINGS
Under-bench
Enclosure
As detailed under Location in the Installation section, adequate ventilation must
be provided for the refrigeration condenser unit.
If the back of the bench is to be enclosed, suitable ventilation grills and baffles
must be fitted into the joinery panels.
Air Flow Baffles
To prevent warm air re-circulating inside the enclosure, baffles must be
constructed to separate the inlet and exit air.
Grill
Dimensions
Each grill, in and out, should have a minimum
open area of 730 cm
2
.
A suitable sheet metal grill may be made by
punching a pattern of 49 rectangular holes, each
40mm x 40mm. The holes may be spaced by
5mm.
Suitable grills can be supplied by FPG, as an
optional extra.
It is not recommended to use louver panels, as
they would have to be very large to achieve the required open area, and be
more prone to becoming blocked with fluff and dust.
Condenser Assy
Air In Grill
Air Out Grill