REFRIGERATED CABINETS  -  SERVICING 

 

Temperature 
Regulator 
XR40CX   

 

Model XR40CX is a microprocessor based 
controller.  
It uses with three NTC probes, the first 
one, for temperature control, is located in 
the return air (air on). The second one, 
located between the fins of the cooling 
coil, measures the defrost termination 

temperature. The third one monitors the condenser temperature for fault 
indication. 

Since the temperature control probe is located on the return air side of the coil, 
(Air On), the measured temperature will be higher than the average air 
temperature inside the cabinet. 

The instrument is fully configurable through special parameters that can be 
easily programmed through the keyboard, or by use of a “hot key”. 

 

XR40CX 
Compressor 
Control 

The regulation is performed according to the 
temperature measured by the thermostat probe 
with a positive differential from the set point: if the 
temperature increases and reaches set point plus 
differential the compressor is started and then 
turned off when the temperature reaches the set 
point value again. 

In case of a fault in the thermostat probe the start and stop of the compressor 
are timed through parameters 

COn

 and 

COF

 

XR40CX 
Defrost Control

 

Parameters are used to control the interval between defrost cycles (IdF), its 
maximum length (MdF) and two defrost modes: timed or controlled by the 
evaporator’s probe (P2P). 

In this cabinet, the start of the defrost cycle is timed, but the cycle will be 
terminated as soon as the defrost probe reaches the pre-determined 
temperature.  

At the end of defrost dripping time is started, its length is set in the FSt 
parameter. With FSt =0 the dripping time is disabled 

Continued on next page 

 

Summary of Contents for IN 4C08S

Page 1: ...Refrigerated Cabinets Square Format...

Page 2: ...re Products Group Limited All rights reserved No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means electronic mechanical photocopying r...

Page 3: ...Series Cabinets 9 Lighting 9 Compressors 9 Controls 10 Control Panel 10 Power and Refrigeration 10 Lights 10 Temperature Controller 10 Temperature Controller Adjustment 10 Preparation 11 Shelf Locatio...

Page 4: ...s 17 Temperature Probes 17 Condensate Container 17 Trays Shelves Air Grills 17 Re assembly 17 Routines 18 Schedules 18 Warning 18 Condenser Radiator 18 Condensate 18 Inspection 18 Fault Correction 18...

Page 5: ...lation Fan 22 Temperature Regulator XR40CX 23 FPG Settings 27 Dixell Default Settings 27 XR40CX Hot Key 28 XR40CX Alarm Signals 29 XR40CX Connections 29 Door Seals 30 Seal Replacement 30 Sliding Doors...

Page 6: ...C18S 35 SPARE PARTS 36 Cabinet Serial Number 36 Location of Glass Parts 37 MECHANICAL DRAWINGS 38 Dimensions 38 IN 4C08S 12S 15S 18S Square Sliding front doors 38 IN 4C08S 12S 15S 18S Square Fixed fro...

Page 7: ...ructions both general and technical tell you how to install operate and look after your inline food service cabinet so that you can receive the full benefits that this cabinet has to offer These instr...

Page 8: ...f service records in the event of compressor failure Any damage or malfunction resulting from the use of non FPG supplied spare parts Specific Exclusions The following are specifically excluded from w...

Page 9: ...d Refrigerated models The cabinet lighting and temperature controls are on the back of the cabinet Lighting All cabinets are fitted with high efficiency LED lighting strips in the ceiling of the cabin...

Page 10: ...ent Caution This controller should only be adjusted by a qualified service technician The controller is set up during manufacture of the cabinet and should not require further adjustment The indicated...

Page 11: ...pport posts Insert the brackets into their new position and push bracket down firmly The brackets may be positioned to give two different degrees of slope to the shelves Refit all shelf trays and door...

Page 12: ...product from either the front or rear doors The cabinet is designed to maintain the temperature of pre chilled product at between 2 and 4 C It is not a refrigerator and consequently if warm product is...

Page 13: ...replacing the products Once the cleaning is finished turn the cabinet on again turn off the lights and shut the doors The cabinet will cool down under minimum load and be ready for the next day s use...

Page 14: ...er Ambient temperature 25 C Adjust store air conditioning Damaged or missing door seal Replace door seal Evaporator coil iced up De ice coil Condenser radiator blocked Remove dust and debris Thermosta...

Page 15: ...ss steel and aluminium surfaces will be damaged Glass All glass should be cleaned using a good quality glass cleaner and a clean cloth DO NOT use abrasive pads or cleaners because they will damage the...

Page 16: ...fficiency and prevent overheating Interior REFRIGERATED CABINETS CLEANING Access to the Cabinet Base Cavity Remove the doors Lift out the deck trays and plastic louvers Remove the two screws securing...

Page 17: ...air flow and degrade cabinet performance Temperature Probes Take care not to damage or move the temperature probes when cleaning the cooling fins One probe is located on the fan side of the cooling c...

Page 18: ...on engineer are mandatory Remove the louvered panel to access the radiator Be very careful not to bend or damage the soft aluminium fins when vacuuming the radiator If the fins are flattened airflow w...

Page 19: ...ut outs are made to the precise measurements shown in the Mechanical Drawings For In Counter and On Counter installations the joinery design must provide unrestricted ventilation for the condenser uni...

Page 20: ...t connected by a plug and socket but is hard wired to the mains supply a means of isolation must be provided If a plug and socket are used they should still be accessible after the cabinet is installe...

Page 21: ...replacing an LED strip check that the power supply is working If there is no dc voltage at the output the power supply should be replaced If there is a dc output the LED strip must be replaced Access...

Page 22: ...compressor may overheat and the cabinet temperature may rise Remove the louvered panel to access the condenser radiator Regular vacuuming will prevent a build up of dust and fluff but mandatory three...

Page 23: ...or by use of a hot key XR40CX Compressor Control The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temper...

Page 24: ...d value DOWN To see the min stored temperature in programming mode it browses the parameter codes or decreases the displayed value To switch the instrument off if onF oFF Not enabled To lock unlock th...

Page 25: ...SET key Press and immediately release the SET key or wait for 5 seconds to display the probe temperature again XR40CX Change the Set point To change the set point value press the SET key for more than...

Page 26: ...a key NOTE 1 If no parameter is present in Pr1 after 3s the noP message is displayed Keep the keys pushed till the Pr2 message is displayed NOTE 2 The set value is stored even when the procedure is e...

Page 27: ...t Continuous cycle duration 0 0 24 0h 0 0 CCS Set point for continuous cycle 55 0 150 0 C 67 302 F 5 COn Compressor ON time with faulty probe 0 255 min 15 COF Compressor OFF time with faulty probe 0 2...

Page 28: ...r AUS EAL did Digital input alarm delay 0 255min 5 Nps Number of activation of pressure switch 0 15 15 odc Compress status when open door no Fan CPr F_C no rrd Regulation restart with door open alarm...

Page 29: ...d CA Serious external alarm i1 F bAL All outputs OFF CA Pressure switch alarm i1 F PAL All outputs OFF XR40CX Alarm Recovery Probe alarms P1 P2 P3 and P4 start some seconds after the fault in the rela...

Page 30: ...al slides into a groove in the door extrusion and can be withdrawn and replaced if damaged A centre seal is fitted between the inner and outer doors The Qlon seal is located in a slot in the aluminium...

Page 31: ...plus base 0 4 m2 1 5 m2 plus base 0 6 m2 2 0 m2 plus base 0 7 m2 2 5 m2 plus base 0 9 m2 Refrigerant R134A R134A R134A R134A Refrigerant Charge Refer to Serial No label 650 g 420 g 600 g 850 g Conden...

Page 32: ...me Faulty Probe C0F 6 6 6 6 Min Defrost Terminate Temp dtE 3 3 3 3 degC Interval Between Defrosts IdF 4 4 4 4 Hrs Display During Defrost dFd DEF DEF DEF DEF rt it SEt DEF Maximum Temperature Alarm ALU...

Page 33: ...nsure that they can use the appliance safely Young children should be supervised to ensure that they do not play with the appliance Performance Aspects The refrigerated cabinets are HACCP compliant wi...

Page 34: ...26125 Rev K August 2018 34 Inline 4000 Series Cabinets ELECTRICAL CIRCUIT DIAGRAMS Model IN 4C08S Inline 4000 Series 800mm Refrigerated Cabinet Model IN 4C12S Inline 4000 Series 1200mm Refrigerated C...

Page 35: ...2S 15S 18S Square Format 35 Future Products Group ELECTRICAL CIRCUIT DIAGRAMS Continued Model IN 4C15S Inline 4000 Series 1500mm Refrigerated Cabinet Model IN 4C18S Inline 4000 Series 1800mm Refrigera...

Page 36: ...D power supply 25922 Top Light Replacement Kit for 4C08 69871 Shelf Light Replacement Kit for 4C08 69839 Top Light Replacement Kit for 4C12 69858 Shelf Light Replacement Kit for 4C12 69869 Top Light R...

Page 37: ...69391 4K 1200 Refrigerated DG Flat Inner Slider Door 69577 4K 1200 Refrigerated DG Flat Outer Slider Door 69576 4K 1500 Refrigerated DG Flat Inner Slider Door 73631 4K 1500 Refrigerated DG Flat Outer...

Page 38: ...t No 26125 Rev K August 2018 38 Inline 4000 Series Cabinets MECHANICAL DRAWINGS Dimensions REFRIGERATED CABINETS MECHANICAL DRAWINGS IN 4C08S 12S 15S 18S Square Sliding front doors Continued on next p...

Page 39: ...IN 4C 08S 12S 15S 18S Square Format 39 Future Products Group Dimensions cont REFRIGERATED CABINETS MECHANICAL DRAWINGS IN 4C08S 12S 15S 18S Square Fixed front glass...

Page 40: ...Part No 26125 Rev K August 2018 40 Inline 4000 Series Cabinets Dimensions cont REFRIGERATED CABINETS MECHANICAL DRAWINGS IN 4C08S 12S 15S 18S Square On counter Versions...

Page 41: ...IN 4C 08S 12S 15S 18S Square Format 41 Future Products Group Dimensions cont REFRIGERATED CABINETS MECHANICAL DRAWINGS IN 4C08S 12S 15S 18S Square In counter Versions...

Page 42: ...nets can be fitted with a rear sandwich preparation shelf as an optional extra Cabinet Variants The drawings show the common overall dimensions for 800mm 1200mm 1500mm and 1800mm cabinets The cabinets...

Page 43: ...IN 4C 08S 12S 15S 18S Square Format 43 Future Products Group...

Page 44: ...change specifications and design without notice AUSTRALIA E ausales fpgworld com T 1800 813 745 CHINA ASIA E asales fpgworld com T 86 21 3351 3390 EUROPE E eusales fpgworld com T 31 6 5253 4769 INDIA...

Reviews: