draught stabilizer (barometric damper) must be
installed to the connector pipe.
2.7. External tank
A barometric fuel tank should not be positioned where
it will be in the direct rays of the sun or adjacent to a
source of intense heat.
If the tank is more than 8 ft (2,5 m) higher than the stove a
pressure reducer must be installed on the oil line (max.
working pressure : 300 mbar).
If the tank is lower than the stove a lift pump will have to be
utilized.
A clearance of 6 “ (15 cm) must be maintained between
the external/remote tank and the stove.
2.8. Levelling
It is essential to ensure that the appliance sits level on
the floor. Adjust the levelling feet (fig. 8).
Use a spirit level across the burner pot to check the
level (fig. 10).
2.9. Pre-utilisation check
Check the condition of the filler seals, that the door
closes correctly, that the window is not damaged, that
the smoke passages are not obstructed by packaging
or removable parts. All removable parts, fuel retainer,
baffle, must be correctly installed.
2.10. Oil flow adjustment
The float regulator has been adjusted at the factory and
should not need further adjustment. If the burner does
not work correctly, check possible causes before
readjusting the settings :
- Chimney draught
- Fresh air inlet
- Oil supply.
Low setting (Refer to # 2, fig. 12) :
- set the regulating knob on “1" and let the burner run
for a few minutes. The flame must completely cover the
bottom of the burner and the catalyser body must be
glowing red hot.
- if the flame is too small, the stove will soot up quickly ;
increase the flame by turning the setting screw (# 2)
A
Figure 9 - Fitting the tray
Figure 10 - Burner level check
1
5
3
6
2
7
1
3
4
6
2
7
Figure 11 - Gravity or pumped oil supply
1 - 2,5 m maxi
2 - At least 0,25 m
3 - Oil Tank
4 - Filter
5 - Suction pump with
reserve and filter
6 - Pipe Ø 6x8 mm
7 - At least 0,15 m
1
2
3
Figure 12 - Adjustment devices
1 - Adjustment of the draught regulator
2 - Adjustment screw for low setting
3 - Adjustment screw for high setting
Document n° 979-3 EN ~ 28/02/2000
174 05 05
BELFORT
Oil fired stove
6
Technical manual