ZMI
_001_
2030
0190
84-F
A
ID0
006_
#SEN_
#
AQU_
#V1.
fm
- 4 -
2. Key
Warning!
Failure to observe can result in bodily injury or even death.
Caution!
Failure to observe can result in material damage.
☞
Important!
Failure to observe can cause the product to malfunction.
☞
Useful information for optimum handling of the product.
3. Warranty
Liability is accepted in accordance with the General Terms and Conditions of
Business and Supply.
Use only genuine spare parts!
4. Important notes
• Installation, commissioning and maintenance must be performed only by a
qualified expert in accordance with the instructions provided, legal requirements
and recognised engineering standards.
• All technical connection regulations specified by the local water and electricity
supply companies must be observed.
• We reserve the right to make changes.
5. Application
Emergency showers are prescribed first aid installations for work stations where
hazardous materials are being handled.
6. Technical specifications
Minimum flow pressure:
0.5 bar
Maximum stagnation pressure:
10 bar
Volumetric flow:
0.5 bar flow pressure:
45 l/m
1.0 bar flow pressure:
65 l/m
1.5 bar flow pressure:
80 l/m
2.0 bar flow pressure:
90 l/m
2.5 bar flow pressure:
100 l/m
3.0 bar flow pressure:
110 l/m
Assembly height:
Lower edge of shower head (220 ± 10) cm
above floor as per EN 15154 Part 1